background image

1

!

OPEN CIRCUIT INDICATION

!

NEMA 4X/IP65 SEALED FRONT BEZEL

!

USER PROGRAMMABLE INPUT

(Thermocouple types T, E, J, K, R, S, B, N, or mV)

!

PROGRAMMABLE TEMPERATURE OFFSET

!

SELECTABLE F or C WITH 1 or 0.1 RESOLUTION

!

F OR C DISPLAY ANNUNCIATORS

!

CONFORMS TO ITS-90 TEMPERATURE SCALE 

!

COLD JUNCTION COMPENSATION (Enable/Disable)

!

0.48 INCH (12.2 mm) HIGH DIGITS

!

5 DIGIT LCD, POSITIVE REFLECTIVE OR NEGATIVE

TRANSMISSIVE WITH RED BACKLIGHT

DESCRIPTION

The CUB4TC is a 9 to 26 VDC powered, microprocessor based temperature

indicator, with decimal display, for use with T, E, J, K, R, S, B, or N
thermocouple sensors. A mVDC display mode with a range of -10.00 to 60.00
mV is also selectable. Programmable features include thermocouple type, cold
junction compensation, Fahrenheit, Celsius, or millivolt display, input filtering,
input filter range, and a user offset. The 0.48", 5 digit LCD display provides
annunciators for Fahrenheit or Celsius indication and is available with or
without a backlight.

SAFETY SUMMARY

All safety related regulations, local codes, and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.

SPECIFICATIONS

1. 

DISPLAY:

Reflective LCD or Transmissive LCD with red backlight, 5 digit

display 0.48"(12.2 mm) height, F or C annunciators.

2. 

POWER:

9 to 26 VDC @ 65 mA with backlight, 25 mA without backlight.

Reverse polarity protected.
Must use the MLPS or a Class 2 or SELV rated power supply.

Backlight version only

: 0.15 

°

C/Volt CJC error if powered from other than

12 VDC. May be compensated with offset.
Example: 24 VDC supply, (24V-12V)*0.15 °C/V = 1.8 °C, 

Enter -1.8 °C user offset.

3.

INPUT:

Isolation

: TC+ and TC- terminals are not electrically isolated from the power

supply.

Response Time

: 500 msec.

Failed Sensor Display

OPEN

Overrange/Underrange Input

OLOL

/

ULUL

Overrange/Underrange Display

: “

.....

”/“-

.....

” 

Normal Mode Rejection

: 40 dB @ 50/60 Hz

Common Mode Rejection

: 100 dB @ DC to 60 Hz

Maximum Input Voltage

: 30 VDC, TC+ to TC-

Maximum Input Voltage TC-

:  3 VDC max. with respect to common

Thermocouple

: Conforms to ITS-90.

Types

: T, E, J, K, R, S, B, N

Input Impedance

: 20 M

Lead resistance effect

: 0.25 

µ

V/ohm

Cold junction compensation

: Less than 1.0 °C over 0 to 50 °C ambient

temp range.

Resolution

: 1 °C/F all types, or 0.1 °C/F for T, E, J, K and N only.

4. 

TEMPERATURE EFFECTS:

Span Drift

150 ppm/°C Max.

Zero Drift

< 1 

µ

V/°C Max.

MODEL CUB4TC - INTELLIGENT THERMOCOUPLE INDICATOR

CAUTION: 

Read complete instructions prior to installation and

operation of the unit.

DIMENSIONS  In inches (mm)

Note: Recommended minimum clearance (behind the panel) for

mounting clip installation is 2.1" (53.3) H x 3.0" (76.2) W.

PANEL CUT-OUT

Bulletin No.  CUB4TC-E
Drawing No.  LP0351
Released  3/04

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

UL Recognized Component,
File # E179259

MODEL

DESCRIPTION

PART NUMBER

MLPS

CUB4TC

Thermocouple Indicator, Reflective LCD

CUB4TC00

Micro Line/Sensor Power Supply

Thermocouple Indicator, Red Backlit Transmissive LCD

MLPS0000

CUB4TC20

ORDERING INFORMATION

Summary of Contents for CUB4TC

Page 1: ...R 9 to 26 VDC 65 mA with backlight 25 mA without backlight Reverse polarity protected Must use the MLPS or a Class 2 or SELV rated power supply Backlight version only 0 15 C Volt CJC error if powered...

Page 2: ...nputs The shield screen pigtail connection should be made as short as possible The connection point for the shield depends somewhat upon the application Listed below are the recommended methods of con...

Page 3: ...ram Menu of the CUB4TC is accomplished by breaking the electrical connection between the PROGRAM terminal and the COMM terminal During exit of programming the unit displays SAVE to indicate that the d...

Page 4: ...ffect the accuracy of the CUB4TC Voltage Calibration Check 1 Enter the programming menu and set tYPE to LIN and OFSEt to 0 Exit programming 2 Use a precision DC voltage supply with an accuracy of 0 03...

Page 5: ...ents for indoor use when properly installed The units are intended to be mounted on an enclosed panel The viewing window and buttons are factory sealed for a wash down environment A sponge rubber gask...

Page 6: ...iability under this limited warranty shall extend only to the repair or replacement of a defective product at The Company s option The Company disclaims all liability for any affirmation promise or re...

Page 7: ...7 This Page Intentionally Left Blank...

Page 8: ...402 Tel 1 717 767 6511 Fax 1 717 764 0839 Red Lion Controls Asia 31 Kaki Bukit Road 3 06 04 05 TechLink Singapore 417818 Tel 65 6744 6613 Fax 65 6743 3360 Red Lion Controls BV Basicweg 11b NL 3821 BR...

Reviews: