Servicing The Red Jacket LPG Pump-Motor Unit
Maintenance of the Red Jacket Submersible LPG Pump-Motor Unit
31
Maintenance of the Red Jacket Submersible LPG Pump-Motor Unit
There is not a requirement for initial bearing running-in period for the Red Jacket submersible LPG pump-motor
units. There is also no required maintenance or servicing frequency for the pump-motor unit. All components of the
pump-motor unit are designed to last for many years.
Yearly Inspections
Check pump capacity, pressure, and power. If the pump performance does not satisfy your process requirements,
the pump-motor unit should be removed from the storage vessel and inspected. A Red Jacket submersible
Premier, Premier Mid-Flow or Premier Hi-Flow LPG pump is not repairable. The pump and motor of all three must
be replaced as a complete set, not individually unless prior approval from Veeder Root is received.
Figure 10. Service Parts
Table 11. Service Parts List
Item No.
Part Number
Qty.
Description
1
410211-001
1
Gasket
2
144-220-5
1
Discharge Head Fastener Kit - contains (4) socket head screws and (4) lock
washers
3
072-725-1
1
O-ring, motor (25.4 x 1.8 mm [1.0 x 0.070 in.])
4
144-210-1
1
Pump fastener kit - contains (4) hex head screws and (4) lockwashers
5
410156-001
1
Pigtail connector, 14 AWG, 6 meter (20 ft.)
6
410109-001
1
Discharge head O-ring kit
5
6
3
1
2
2
4