Installing A Red Jacket Submersible LPG Pump-Motor Unit
Typical System Schemes with Submersible LPG Pump-Motor Unit
26
Figure 8. Typical Scheme For An Aboveground LPG Storage Tank With Horizontal Submersible Pump-Motor Unit
Table 10. Minimum Design Requirements Horizontal Manifold
Premier
Nomenclature: LPG300V17-21
Excess flow valve (Inlet) minimum 462 liter/min. (122 gallon/min.) liquid
Ball valve 2”
Manifold: 6.9 in. (175 mm) minimum
Outlet: 1-½ - 2 in.
Vapor return line ¾ in.
Excess flow valve (Vapor return line): minimum 78 liter/min. (20 gallon/min.)
Pump unit must be supported by three support-arms: a. the inlet, b. discharge-head, and c. at the pump
flange (i.e., /DSI PA/PE 4-38 Pipe Isolator)
Manifold : must be installed 4 - 5º upwards to avoid vapor lock in manifold
Premier Midflow
Nomenclature: LPG300V17-17
Excess flow valve (Inlet) minimum 462 liter/min. (122 gallon/min.) liquid
Ball valve 2”
Manifold: 6.9 in. (175 mm) minimum
Outlet: 1-½ - 2 in.
Vapor return line ¾ in.
Excess flow valve (Vapor return line): minimum 78 liter/min. (20 gallon/min.)
Pump unit must be supported by three support-arms: a. the inlet, b. discharge-head, and c. at the pump
flange (i.e., /DSI PA/PE 4-38 Pipe Isolator)
Manifold : must be installed 4 - 5º upwards to avoid vapor lock in manifold
DISPENSING
COLUMN
FILLING
POINT
LPG STORAGE
VESSEL
LPG PUMP
16
14
16
1
2
4 20
26
2"
3/4"
1-1/4"
8
21
24
23
22
13
12
9
25
28
15
2"x3/4"
MAX. LIQUID
LEVEL
MANHOLE
NAMEPLATE
MANHOLE
LIFTING LUG
VAPOR SEPARATOR
EXPANSION VESSEL
PRESSURE GAUGE
FLANGED VALVE
FLANGE
VAPOR LINE
LIQUID LINE WITH
DIRECTION ARROW
OVERFILL PROTECTION
PRESSURE
VALVE
DIFFENTIAL
21
1
16
8
14
16
13
2"x3/4"
27
3/4"
22
2"x3/4"
7
17
30
TO GAS ACTUATORS
2"
10
3
29
1/2"
PIPE CAP
5
4
7
16
20
11
2"
rj/051-327/fig6.eps
Summary of Contents for LPG Premier
Page 38: ......
Page 39: ......
Page 40: ...For technical support sales or other assistance please visit www veeder com...