INSTALLING AN OUTPUT BOARD

1. Remove the controller from the case.

2. Lift up on the top bezel board latch while gently pulling out on the bezel/

display board assembly. Do NOT remove the display board from the 

bezel.

3. Remove the output board by pulling it away from the other boards. 

Replace the output board by aligning the board to board connector. Be 

certain the connector is fully mated.

4. Connect the bezel/display board assembly  by guiding the board ends into 

the bezel latches. Slide the assembly on evenly until the display board 

connector is completely engaged and bezel latches are fully seated onto 

the boards.

Note: When replacing the output board, be certain to install a new output 

board of the same type. Appropriate rewiring considerations must be given if 

the output board type is changed.

T48/P48/TLA OUTPUT BOARD

MD1797

D

P

%P

DV

MN

A1

A2

EB0783

CONNECTOR

BOARD

DISPLAY

O1

LATCH

BEZEL BOARD

BOARD ASSEMBLY

BEZEL/DISPLAY

SECOND INPUT/RS485 BOARD *

POWER 

BOARD

SUPPLY

CPU BOARD

%P

* MODEL NUMBER DEPENDENT

D

P

DV

MN

O1

A1

A2

CONNECTOR

OUTPUT BOARD

MD1797

EB078

3

EB078

4

OUTPUT BOARD

AL1

O1

AL2/O2

BOARD

OUTPUT

RELAY

OUTPUT BOARD

LOGIC/SSR DRIVE

AL1

O1

AL2/O2

LIMIT

AL1

#RBDLA210

Output Board

Form-C Relay

Bulletin No.  RBD48-D
Drawing No.  LP0347
Released  06/13

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

Caution: The bezel assembly contains electronic circuits that can be damaged by static electricity. Before removing the assembly, discharge static charge on 

your body by touching an earth ground point. It is also important that the bezel assembly be handled only by the bezel itself. When handling a circuit board, be 

certain that hands are free from dirt, oil, etc., to avoid circuit contamination that may lead to a malfunction.

SPECIFICATIONS & TYPICAL CONNECTIONS

Relay Connections

RBD48 Relay Outputs:

Type:

 Form-A (Shared common for the Alarms)

Contact Rating:

 3 A @ 250 VAC or 30 VDC (resistive load)

RBDLA Relay Outputs:

Limit Relay Type:

 Form-C

Alarm 1 Relay Type:

 Form-A

Contact Rating:

 5 A @ 250 VAC or 30 VDC (resistive load)

Life Expectancy:

 100,000 cycles at max. load rating. (Decreasing load and/

or increasing cycle time, increases life expectancy.)

To prolong contact life and suppress electrical noise interference due to the 

switching of inductive loads, it is good installation practice to install a snubber 

across the contactor. Follow the manufacturer’s instructions for installation.

Note: Snubber leakage current can cause some electromechanical devices to 

be held ON.

CONTROLLER

LOAD

FUSE

01

AC/DC 

POWER

N.O.

COMM.

LOAD

LOAD

FUSE

AC/DC

POWER

AL2/02

AL1

N.O.

COMM.

N.O.

Main Control Output

Alarm Outputs/Cooling

Reviews: