5
INSTALLATION INSTRUCTIONS
THIS INSTRUCTION MANUAL MUST BE READ IN CONJUNCTION WITH THE
VEKTOR XL INSTALLATION AND OPERATING INSTRUCTION MANUAL
INSTALLATION CODES
Note appliance gas type
– Natural gas. Should the appliance be the incorrect gas type, please
contact the supplier.
Installers
– Please ensure the installation and instruction manuals supplied with this appliance are
supplied to the customer and the customer is trained on how to operate the appliance correctly.
Do not modify the appliance.
Do not exceed maximum rated pressures.
Appliance must be installed with gas installation code (AS/NZS5601.1-2013) and applicable
electrical installation code (AS3000).
Test for gas leaks prior to operating appliance. Check
gas pressures and adjust if incorrect.
FLUE CONFIGURATIONS
For flue configurations 0-5m (aluminium flexible flue only)
– Refer to Vektor XL instruction
booklet.
Where lengths greater than 5m are required the inlet is run completely in aluminium flexible flue,
the first 5m of the outlet flue (hot exhaust) is run in flexible aluminium flue, then a poly flue system
is used that requires drainage points to allow for condensation removal.
– Note drain fall direction
is different for rooftop flues.
– Refer XLC Rooftop instruction.
Aluminium flue connections must be sealed with a suitable sealant.
Recommended Silicon
– Non-acetic, neutral cure 150degc or higher temperature rated. Bostik
RTV 926 or similar
Wall mounted fan module
– terminal must be installed with clearances as specified by AS5601.1-
2013 Clause 6.9.3
Run air intake flue as required
– Maximum run 14m. Flues can be run next to each other. Maintain
clearances to combustibles