A Contact ID Configuration
Alarm Panel Setup and Connection
Configure the Alarm Panel as follows:
®
Communicator format
Ademco Contact ID
(Automatic Reporting)
Primary Tel Number
1234
Account Code
1234
Dialing Type
Tone
Wait for Dial Tone
No
Note:
The account code programmed into the alarm panel is not
used by the alarm transmitter. The alarm transmitter is
preprogrammed internally with the appropriate radio code, however
for the correct functioning of the Contact ID interface, the alarm
panel is still expected to supply an account code.
Connect the TIP (input 8) of the transmitter to the TIP input of the
alarm panel. Connect the RING (NEG input) of the transmitter to the
RING input of the alarm panel.
Note:
The NEG input of the transmitter must also be connected to
the NEG terminal of the battery, as is the case for normal transmitter
installations.
When programming the alarm panel, the following must be
observed:
Up to 4 partitions are supported / reported
!
Up to 31 zones are reported
!
(zone 32 reserved for universal or unknown zone)
Up to 15 users / key holders are reported
!
(user 16 reserved for universal or unknown user)
Only battery low and AC fail restorals are reported
!
All standard RDC type telemetries are reported
!
B Hardwired Input Configuration
Certain hardwired inputs are still functional while the transmitter is
configured for Contact ID type operation. It is however highly
recommended that these inputs should only be connected if the
Contact ID interface is not being used. Connecting the hardwired
inputs and using the Contact ID interface simultaneously will cause
the transmitter to send huge volumes of redundant transmissions,
which in turn will cause the radio network reliability to decrease.
Input 1
- Panic
Input 2
- Alarm
NB: Inputs 3, 4, 5, 6, 7 & 8 are not available for use and
therefore have no terminal blocks. These inputs should not be
connected under any circumstances.
Input 2 - Alarm Input
This input has a programmable delay feature to allow direct
connection to the bell output of alarm panels. The delay prevents
triggering when annunciation is used. The delay is programmable
between 0 - 7.5 seconds in 0.5 second intervals.
The transmitter inputs accommodate the following alarm panels
output voltage ranges:
Positive Trip
10.8 ~ 14V
Negative Trip
Open Collector 0 ~ 0.5V
Alarm panels which do not meet this requirement will require a level
converter interface.
24hr Standby
082 444 7176
TX790CID
(Contact ID)
-
Installation Instructions
TIP
X -
CAUTION
- do not use
Alarm
Panic
RING
(to alarm panel Telco jack)
(to alarm panel Telco jack)
Squeeze the
lid firmly on
both sides just
below the
mounting holes
to remove the lid
Recommended mounting
screws and plugs
M4.5 x 30 mm
countersunk head
self tapping
6 x 35 mm
Mounting screws and
plugs not included
www.radiodata.co.za
Transmitter standby -
battery voltage correct
Transmitting
Mains fail
Battery voltage too low for normal operation
Low battery, but still able to operate
Battery over voltage
Incorrectly programmed
LED indicates transmitter conditions:
Engineer test button
1
2
V
S
E
R
IA
L
A
C
J
A
C
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
J
u
m
p
e
rs
f
o
r
n
e
g
a
ti
v
e
t
ri
p
Rev 16 0911