Door control
FireProV2
Manual
Please keep this manual with attachments carefully!
28
10.7
BM (Fire alarm) function
If the BMC (Fire alarm Contact) is activated the door will close because the voltage on the electric
brake of the motor is disconnected. At factory default settings, the door drops until the close limit
switch is reached. If the door has to be lowered further than the close limit switch or to another
position the additional limit switch (S6) can be used as "overclose" limit switch. To achieve this,
parameter 3.1 must be set to setting 2.
The normal Open button can be switched on or off with parameter 3.3 if the BM function is active.
If it is active, the door will open hold to run, and when releasing it immediately close again.
The BM function can be extended after the BMC input is closed . This is adjustable with
parameter 3.4 from 0 to 240 second.
An input is available to connect an escape button. By activating this button, the door will open.
This can be completely open or the extra limit switch can be used to set an intermediate position so
that the door or roller shutter goes partial open (parameter 3.1 to 3). If the waiting time, which is
adjustable from 1 to 240 second in Parameter 3.2, is reached the door/roller shutter will close .
During this waiting time, the button can be used to close the door/roller shutter immediately.
This intermediate position can also be used to make a stopover (parameter 4.1) when closing while
the BMC contact is active. The door/roller shutter first drops to this position and will wait for a set
time (parameter 4.2) and then close further.
10.8
RM (Smoke detection) with Reset function
In the case of smoke, the same as a fire alarm occurs. Here are two options that can be chosen with
parameter 4.3. The first is to allow the roller shutter to close completely. If the door/shutter is
completely closed, an output indicates that the air bellows of the door/roller shutter can be filled.
The door/roller shutter can now no longer be opened, so the escape functions are now disabled. If
the smoke detection is over, a reset command must first be offered after the door/roller shutter is
cleared again.
After the reset command, the door will only be active after a set time (parameter 4.5). In the
meantime, the door cannot be operated. Only then will the door/roller shutter function normally.
The second option is to send the door/roller shutter to a partial opening. In the case of digital limit
switches, the door/roller shutter (If the mains supply is still present) opens to a partial opening. In
the case of CAM/mechanical limit switches, the door/roller shutter will be sent open if it is located
between the limit switch positions. If the position is above the set position, the door will first open
completely and then close to the set position, This is only possible if the mains supply is still
present.
Opening is only possible if the mains supply is still present.
If the mains power is switched off, can with parameter 4.4 be chosen if the door/roller shutter
should remain in position if not open at the end position or at DES below the set partial opening.
Or you can choose to close the door/roller shutter completely if it is below the set position.