RCF S.P.A. THANKS YOU FOR PURCHASING THIS PRODUCT, WHICH
HAS BEEN DESIGNED TO GUARANTEE RELIABILITY AND HIGH
PERFORMANCES.
WARNING: Any change made by unauthorized personnel to the
product and / or the system (in which it is installed and configured,
including rack cabinet and wiring) may invalidate the CE marking
(certification EN54-16: 2008) and also the product warranty.
DESCRIPTION
BM 9802 is a desktop paging microphone exclusively dedicated for the RCF
DXT 9000 system.
It can be directly connected to a main unit (i.e. MU 9186, MX 9502, MX 9504)
through a four-pair J-type fire-rated cable.
It is possible to link up to sixteen BM 9802 paging microphones (or
alternatively, the BM 9804 model, which has three assignable buttons) to each
main unit bus (total: max. 32 paging microphones).
Their configuration (in terms of access) can be set by the dedicated PC software.
Its front panel has a numeric keyboard for zone selection.
All paging microphones also have the ‘Push To Talk’ (PTT), the ‘General Call’
and the ‘Chime’ (On/Off) buttons.
Up to eight BE 9808 keyboards can be linked to every BM 9802 (not used for
emergency purposes).
Each BE 9808 has eight buttons that can be set (by using the dedicated PC
software) to:
-
Select zones or zone groups.
-
Recall presets.
-
Increase / Decrease the background music volume.
-
Mute / unmute the background music.
-
Fault acknowledgement.
-
Reset evacuation / alert events.
-
Stop (without resetting) evacuation / alert messages.
-
Reactivation of evacuation / alert messages.
-
Fault indication.
-
Activation of all-clear, test and routine messages.
The paging microphones used for emergency purposes (the first of each bus)
can have max. four BE 9808 and their ALARM button can be enabled.
All paging microphones need to be powered by external 24 V dc adapters (500
mA, i.e. optional RCF AC AD 2405).
The first paging microphone of each bus can be used for emergency purposes.
In this case, the paging microphone shall be directly powered by the DXT 9000
system main unit (no need of an external adapter, but it will be necessary to
set an internal switch) as required by the EN 54-16 standard.