ST-72 User's Manual
Document: UM-1007
Revision Level A
8
1.3.5
ZONE SCREEN
The ST-72 Zone screen displays the eight possible zones simultaneously. If an alarm
condition occurs the user will be able to quickly see in what zone the situation is
occurring. Each active zone is divided into alarm levels which are green until an alarm is
present. Inactive zones and alarm levels are grayed out. If an alarm should occur, the
zone name field will flash and the corresponding box in the assigned zone will turn the
color of the alarm that is present or alternate if two different colors are present. Once
the alarm has been acknowledged the name field will stop flashing. Utilizing the Display
Alarm feature in the Systems Configuration menu allows new alarms to always force the
LCD to the Zone screen. This is useful for applications requiring zones with alarms to be
displayed. If the Zone feature is not utilized this screen can be turned off in the Systems
Menu.
The Zone screen is also helpful for configuring the different zones. To display all the
channels included in any zone, press
Edit
while in the Zone screen. This will cause a
blue box to outline one of the zones. Use
/
/
/
to select the correct
zone and press
Edit
again. The Main Data screen will appear with all the channels that
are included in the selected zone displayed in color and the channels that are not in the
selected zone grayed out. Any channel needed to be included or excluded from the
selected zone can be selected and configured from this screen.
North Entrance
A1
A2
A3
F
Control Room
A1
A2
A3
F
ZONE 8
A1
A2
A3
F
ZONE 7
A1
A2
A3
F
Main Process
A1
A2
A3
F
Switchgear Room
A1
A2
A3
F
Tank Farm
A1
A2
A3
F
West Gate
A1
A2
A3
F
Summary of Contents for ST-72
Page 106: ...ST 72 User s Manual Document UM 1007 Revision Level A 100...
Page 108: ...ST 72 User s Manual Document UM 1007 Revision Level A 102 Figure 6 4...
Page 128: ...ST 72 User s Manual Document UM 1007 Revision Level A 122 8 5 3 COPY CHANNELS Figure 8 7...
Page 129: ...ST 72 User s Manual Document UM 1007 Revision Level A 123 8 5 4 PROGRAMMABLE RELAYS Figure 8 8...