RBI 8900 Series Installation & Operation Manual Download Page 8

SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS

Page 8

CHIMNEY & VENT PIPE 
CONNECTIONS

WARNING: The vent installation must be in 
accordance with Part 7, Venting of Equipment, of 
the National Fuel Gas Code, ANSI Z223.1/NFPA 
54-latest revision or applicable provisions of the 
local building codes. Canadian installations must 
comply with CAN/CGA B149.1 or .2 Installation 
Code. Improper venting can result in excessive 
levels of carbon monoxide which can result in 
severe personal injury or death!

Chimney Inspection & Sizing

A thorough inspection of the masonry chimney must be 
performed to ensure that the chimney is clean, properly 
constructed, lined and sized. Exterior masonry chimneys 
should not be used unless properly lined to prevent 
condensation and draft problems. Table 3A and 3B lists 
the equivalent breeching and fl ue sizes required for the 
boiler/water heater.

Table 3A - Equivalent Breeching & Chimney Size

 

Model 

 Size Model Size

 Size 

 

in

 

 mm

 Size   

in

  

mm

 

  420 

10

  

254

 1580 

18

  

457

 

  530 

10

  

254

 1685 

18

  

457

 

  630 

12

  

305

 1790 

20

  

508

 

  735 

14

  

356

 1900 

20

  

508

 

  840 

14

  

356

 2000 

22

  

559

 

  950 

14

  

356

 2400 

24

  

610

 1050 

16

  

406

 2800 

26

  

660

 1160 

16

 

406

 3200 

28

  

711

 1260 

16

 

406

 3600 

30

  

762

 1370 

18

  

457

 4000 

30

  

762

 1470 

18

  

457

Note:  These sizes are based on a

 20 ft, 

6.1m

 

chimney height.

Table 3B - Equivalent Breeching & Chimney Size Dual Flue

 

Model 

 Size Model Size

 Size 

 

in

 

 mm

 Size   

in

  

mm

 

  840 

10

  

254

 1790 

16

  

406

 

  950 

10

  

254

 1900 

16

  

406

 1050 

12

  

305

 2000 

14

 

356

 1160 

12

  

305

 2400 

16

 

406

 1260 

12

  

305

 2800 

18

 

457

 1370 

14

  

355

 3200 

20

 

508

 1470 

14

  

355

 3600 

22

  

559

 1580 

14

 

355

 4000 

22

  

559

 1685 

14

 

355

Note:   Minimum vertical rise off top dual fl ue units: 

3 ft

1 m

 (sizes  

            840-3200),

 5 ft

1.5 m

 (sizes 3600-4000).

When more than one appliance is connected to the 
same chimney fl ue, the fl ue must be large enough to 
safely vent the combined output of all the appliances.

WARNING: If an appliance using any type of a 
mechanical draft system operating under 
positive pressure is connected to a chimney 
fl ue, never connect any other appliances to this 
fl ue. Doing so can result in the accumulation of 
carbon monoxide which can cause severe 
personal injury or death!

Vent Connections

Always use a type B or single wall galvanized metal vent 
pipe the same diameter as the draft diverter fl ue collar. 
Use the shortest, straightest vent system possible for 
the installation. If horizontal runs exceed 

6 ft

1.8 m

 they 

must be supported at 

6 ft

1.8 m

 intervals with overhead 

hangers. The vent system should be sloped up toward 
the chimney at a minimum rate of 

1/4 in/ft

20 mm/m

 

and terminate fl ush with the inside of the chimney fl ue. 
Fasten each connection with at least 3 corrosion 
resistant sheet metal screws.

WARNING: Never modify or alter any part of the 
boiler’s draft diverter. This includes the removal 
or alteration of any baffl es. Never install a vent 
pipe of a diameter different than that of the 
boiler draft hood fl ue collar. Failure to comply 
with this warning can result in severe personal 
injury or death.

Always provide a minimum clearance of 

6 in

152 mm

 

between type C vent pipe and any combustible 
materials. Type B1 vent may be used, clearance between 
it and any combustible material must be as listed.

WARNING: Failure to maintain minimum 
clearances between vent connectors and any 
combustible material can result in a fi re causing 
extensive property damage, severe personal 
injury or death!

To determine the appropriate power venter for the boiler/
water heater, see Table 4, Power Venter Sizes. Follow 
the power venter manufacturer’s installation instructions.

Table 4 - Power Venter Sizes
 

8900 

Power Venter 

Max. Pipe Length

 

Model  

Size 

FT  

m

 420-530 

HS-2 

100

 

31

 630 

HS-3 

100

 

31

 735-1160 

HS-4 

100

 

31

 1260-1900 

HS-5 

100

 

31

Models 2000-4000 - Consult Tjernlund

Summary of Contents for 8900 Series

Page 1: ...or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch d...

Page 2: ...8800 and 8900 finned copper heating boiler water heater pool heater To obtain the safe dependable efficient operation and long life for which this heating boiler water heater was designed these instru...

Page 3: ...mum site will be level central to the piping system close to a chimney and have adequate fresh air for combustion Ensure that the boiler water heater is level from front to back and from side to side...

Page 4: ...a confined space minimum clearances listed in Table 1 or 1A must be maintained between the boiler water heater and any combustible construction When installed in a confined space Figures 1 2 3 4 and 5...

Page 5: ...he free area necessary to meet the make up air requirements of the enclosure consideration must be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh size of...

Page 6: ...age 6 Figure 2 Vertical Venting Using A Masonary Chimney And Inside Air 8900 8800 Series Figure 3 Dual Flue Outlets And Inside Air 8900 8800 Series 10 FT 3 1 m 3 FT 1 m 5 FT 1 52 m 3 FT 1 m 10 FT 3 4...

Page 7: ...0FT 3 1 m 3 FT 1 m 5 FT 1 52 m PITCH PIPE DOWN TOWARDS TERMINAL CAP 1 4 IN PER FOOT 20MM M OF RUN TO ALLOW FOR CONDENSATE DRAINAGE BUILDING OVERHANG 4 FT 1 2 M MAX 3 FT 9 m 1 5 FT 0 5m MINIMUM DISTANC...

Page 8: ...large enough to safely vent the combined output of all the appliances WARNING If an appliance using any type of a mechanical draft system operating under positive pressure is connected to a chimney f...

Page 9: ...ord s au syst me d vacuation commun et tous les ventilateurs d extraction comme les hottes de cuisin re et les ventilateurs des salles de bain S assurer que ces ventilateurs fonctionnent la vitesse ma...

Page 10: ...y piping adjacent to the boiler outlet connection CAUTION Failure to properly install the flow switch may result in damage to the boiler water heater heat exchanger voiding the warranty HEATING SYSTEM...

Page 11: ...ow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop GPM Ft L s kPa GPM Ft L s kPa GPM Ft L s kPa GPM Ft L s kPa 4 0 4 3 4 7 5 0...

Page 12: ...ow Return Water Temperatures To prevent the problems associated with condensation of the products of combustion due to low return water temperatures a primary secondary piping system with a bypass and...

Page 13: ...guration and valving Check with local codes and ordinances for specific requirements Adjustment Procedure To Maintain Inlet Temperature Above Dew Point T1 Temp Min 110 For Atmospheric T1 Temp Min 125...

Page 14: ...s furnished with factory mounted outlet water temperature gauge 4 Boiler pump purging required Use terminals supplied 5 Secondary loop pipe diameter must be sized large enough to handle maximum flow t...

Page 15: ...tion of the pump size and temperature rise A cupro nickel heat exchanger may also be required The manufacturer should be consulted when these water conditions are encountered See Table 7A CAUTION The...

Page 16: ...elow can be employed to prevent this condition from occurring A balancing valve should be installed on the outlet side of the water heater for purposes of adjusting the flow rate through the heat exch...

Page 17: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 17 Table 7B 8900 Pumping Performance RequirementTable...

Page 18: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 18 Table 7B 8800 Pumping Performance RequirementTable...

Page 19: ...formance Table before making selection 6 Common piping must be sized for maximum combined heater flow 7 Hot water tanks should be equipped with a combination temperature pressure relief valve 8 MA Cod...

Page 20: ...type of gas available at the installation site call the nearest RBI representative to resolve the problem NOTE A minimum gas supply presssure of 6 in 152 mm W C natural or 11 in 279 mm W C propane and...

Page 21: ...diagram supplied with the boiler water heater for proper wiring connections GENERAL OPERATION WARNING Before proceeding read and fully understand the instructions contained in this manual Do not attem...

Page 22: ...n interrupteur ne pas vous servir des t l phones se trouvant dans le b timent Appelez imm diatement votre fournisseur de gaz depuis un voisin Suives les instructions du fournisseur Si vous ne pouvez r...

Page 23: ...reil ne se met pas en marche suivez les instructions intitul es Comment couper l admission de gaz de l appareil et appelez un technicien qualifi ou le fournisseur de gaz inches W C mm W C Natural 3 5...

Page 24: ...anifold pressure tap plug CAUTION Never force the regulator adjustment screw beyond the stop limits or damage to the regulator will occur PROPANE GAS Optimum results are obtained when the boiler water...

Page 25: ...water is 130 F 54 C The operating control should be set to the lowest setting that will satisfy the consumer s needs WARNING Setting the thermostat or operation control too high can result in scaldin...

Page 26: ...osion or other deposits that would impair the boiler water heater s performance Refer to page 30 8900 or page 39 8800 for component identification Combustion Chamber Inspection 1 Remove the left or ri...

Page 27: ...the GENERAL OPERATION and CHECKING AND ADJUSTMENTS sections of this manual for reference 1 Check the thermostat or operating controls for proper operation 2 A float type low water cutoff device must...

Page 28: ...ose or broken wire between pilot valve and PV MV PV terminals 24V at pilot gas valve leads Replace module Adjust the pilot gas pressure using the pilot regulator Pilot ignition problems can be caused...

Page 29: ...f valve is properly sized for the system never exceed 160 psi Expansion tank is waterlogged Ensure expansion tank is properly sized for the system Expansion tank is isolated Ensure valve between expan...

Page 30: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 30 PARTS LIST MODELS 420 1900 36 33...

Page 31: ...0113 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 RH Lower Front Corner Post 03 0114 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 5 24 Jacket End Panels Upper Lower 72 0016 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 6 Inlet Outlet Header Cast...

Page 32: ...0 0277 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 Burner Tube w Bracket 70 0635 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 NS Burner Spacers 03 0309 1 03 0310 1 03 0311 1 03 0312 1 03 0313 1 03 0314 1 03 0315 1 03...

Page 33: ...1 NS Bracket Refractory Upper End 03 0306 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 NS Bracket Refractory Lower End 03 0307 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 18 End Refractory Panel Left Right 05 0001 2 2 2 2 2 2 2...

Page 34: ...70 0189 1 70 0190 1 70 0191 1 NS Upper Rear Refractory Channel 70 0162 1 70 0163 1 70 0164 1 70 0165 1 70 0166 1 70 0167 1 70 0168 1 70 0169 1 70 0170 1 70 0171 1 70 0172 1 70 0173 1 70 0174 1 70 0175...

Page 35: ...0057 1 27 Jacket Top Panel 03 0001 1 03 0002 1 03 0003 1 03 0004 1 03 0005 1 03 0006 1 03 0007 1 03 0008 1 03 0009 1 03 0010 1 03 0011 1 03 0012 1 03 0013 1 03 0014 1 03 0015 1 27a Jacket Top Panel Du...

Page 36: ...Heat Exchanger Assembly Cupronickel 70 0087 1 Cast Iron Headers 70 0088 1 70 0089 1 70 0090 1 70 0091 1 70 0092 1 70 0093 1 70 0094 1 70 0095 1 70 0096 1 70 0097 1 70 0098 1 70 0099 1 70 0100 1 70 01...

Page 37: ...or LP 24V 11 0375 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Solenoid Valve w Regulator NG 120V 11 0372 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Solenoid Valve w Regulator LP 120V 11 0374 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 35 Man...

Page 38: ...G 10 0019 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 Orifice 47 LP 10 0009 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 Orifice 49 2 000 3 999 LP 10 0010 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 Or...

Page 39: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 39 PARTS LIST MODELS 2000 4000 22 7 36 33 30 8 6 39 42 18 21 25 19 21a...

Page 40: ...et Return Headers ASME 57 0492 24 24 24 24 24 24 NS Heat Exchanger V Baffle 03 1147 15 03 1148 30 03 1149 30 03 1150 30 03 1151 30 03 1152 30 12 Base Frame Assembly 70 1708 1 70 1709 1 70 1710 1 70 17...

Page 41: ...Only 11 0455 1 1 18 End Refractory Panel Left Right 05 0050 2 2 2 2 2 2 19 Center Refractory Panel 853413 4 4 6 8 8 10 20 Corner Refractory Panel 05 0052 4 05 0053 4 05 0054 4 05 0055 4 05 0056 4 05 0...

Page 42: ...4V 70 9013 1 1 1 1 1 1 Ignitor PSE NA185 NG 120V 70 9014 1 1 1 1 1 1 Ignitor PSE NA29 LP 24V 70 0631 1 1 1 1 1 1 Ignitor PSE NA185 LP 120V 70 0632 1 1 1 1 1 1 33 Solenoid Valve w Regulator NG 24V 11 0...

Page 43: ...0007 20 24 28 32 36 40 Orifice 22 4 000 5 999 NG 10 0095 20 24 28 32 36 40 Orifice 25 6 000 7 999 NG 10 0097 20 24 28 32 36 40 Orifice 34 LP 10 0021 20 24 28 32 36 40 Orifice 37 2 000 3 999 LP 10 002...

Page 44: ...the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next ad...

Page 45: ...led instructions for the installation of the venting system design or the venting system components and 2 A complete parts list for the venting system design or venting system d MANUFACTURER REQUIREME...

Page 46: ...nd erosion on the inside of the heat exchanger tubes caused by high water velocity through the tubes and is not covered by the manufacturer s warranty See Installation Instructions for proper pump per...

Page 47: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 47...

Page 48: ...260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782...

Reviews: