RBI 8900 Series Installation & Operation Manual Download Page 15

SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS

Page 15

DOMESTIC WATER SUPPLY PIPING

CAUTION: Proper controls must be used to prevent 
water supplied for domestic use from exceeding 
130°F, 

54 °C

 or a scald injury will occur! When 

higher water temperatures are required for 
appliances such as a dishwasher, a mixing valve or 
some other tempering means must be installed. 
Households with small children may require water 
temperatures less than 120°F, 

49 °C

. Local codes 

must be complied with!

General Piping Requirements

Ensure that the water heater is equipped with bronze 
headers. Piping and components connected to the water 
heater must be suitable for use with potable water. The 
water heater must not be connected to any heating 
system piping or components previously used with a 
non-potable water heating appliance. Toxic chemicals, 
such as those used for boiler treatment, are not to be 
introduced into any potable water used for space 
heating. If a hot water storage tank is used in the system 
it must be equipped with a temperature and pressure 
relief valve that complies with ANSI Z21.22 or CAN-4.4 
and CAN-4.6.

NOTE: The storage tank must be located as close 
to the water heater as possible to prevent excessive 
head loss which will reduce fl ow.

Water Chemistry

The required temperature rise across the water heater 
is based on water having a hardness between 8 and 
18 grains per gallon with a level of dissolved solids not 
exceeding 350 ppm. Water having a hardness less than 
8 grains can cause excessive corrosion of the heat 
exchanger. Water that has a hardness greater than 18 
grains per gallon and/or a level of dissolved solids 
exceeding 350 ppm will require a recalculation of the 
pump size and temperature rise. 

A cupro-nickel heat exchanger may also be required. The 
manufacturer should be consulted when these water 
conditions are encountered. See Table 7A.

CAUTION:  The maximum allowable flow rate 
through a water heater with copper heat exchanger 
on an 8900 is 92 GPM, 

5.8 L/s

 and  is 185 GPM, 

11.7 L/s

 

on single pass. The cupro-nickel heat exchanger 
allows for 100 GPM, 

6.3 L/s

 and 200 GPM, 

12.6 L/s

 on 

single pass.

The maximum allowable flow rate through a water 
heater with copper heat exchanger on an 8800 is 185 
GPM, 

11.7 L/s

 and 370 GPM, 

23.3 L/s

 on single pass. 

The cupro-nickel heat exchanger allows for 200 GPM, 

12.6 L/s

 and 400 GPM, 

25.2 L/s

 on single pass. See 

Tables 6A and 6B.

RBI water heaters are designed to run scale free. Due 
to the extreme variables of water conditions world wide 
it is necessar y to consider pH values and water 
hardness in relationship to scaling. It is crucial to 
consider these two variables when making heat 
exchanger and pump selections. If local water conditions 
are extreme, follow the guidelines in the Heat Exchanger 
Selection Table (Table 7A) and the Pumping Performance 
Table (Table 7B). Scale free operation can be achieved 
by using water with a hardness between 8 and 18 and 
by maintaining the pH between 5 and 9. Follow the 
conditions listed under NORMAL in the table. In some 
areas of the country additional precautions must be 
observed due to unusual characteristics of the local 
water supply. Call the nearest RBI representative for 
details.

To properly size the pump a grain hardness and pH test 
must be taken at the installation site before the order is 
placed. Proper pump sizing will improve heater 
performance and help ensure heater longevity.

Expansion Tank

An expansion tank or other means to control thermal 
expansion must be installed in the water heating system 
if back fl ow prevention devices are installed.

Summary of Contents for 8900 Series

Page 1: ...or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch d...

Page 2: ...8800 and 8900 finned copper heating boiler water heater pool heater To obtain the safe dependable efficient operation and long life for which this heating boiler water heater was designed these instru...

Page 3: ...mum site will be level central to the piping system close to a chimney and have adequate fresh air for combustion Ensure that the boiler water heater is level from front to back and from side to side...

Page 4: ...a confined space minimum clearances listed in Table 1 or 1A must be maintained between the boiler water heater and any combustible construction When installed in a confined space Figures 1 2 3 4 and 5...

Page 5: ...he free area necessary to meet the make up air requirements of the enclosure consideration must be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh size of...

Page 6: ...age 6 Figure 2 Vertical Venting Using A Masonary Chimney And Inside Air 8900 8800 Series Figure 3 Dual Flue Outlets And Inside Air 8900 8800 Series 10 FT 3 1 m 3 FT 1 m 5 FT 1 52 m 3 FT 1 m 10 FT 3 4...

Page 7: ...0FT 3 1 m 3 FT 1 m 5 FT 1 52 m PITCH PIPE DOWN TOWARDS TERMINAL CAP 1 4 IN PER FOOT 20MM M OF RUN TO ALLOW FOR CONDENSATE DRAINAGE BUILDING OVERHANG 4 FT 1 2 M MAX 3 FT 9 m 1 5 FT 0 5m MINIMUM DISTANC...

Page 8: ...large enough to safely vent the combined output of all the appliances WARNING If an appliance using any type of a mechanical draft system operating under positive pressure is connected to a chimney f...

Page 9: ...ord s au syst me d vacuation commun et tous les ventilateurs d extraction comme les hottes de cuisin re et les ventilateurs des salles de bain S assurer que ces ventilateurs fonctionnent la vitesse ma...

Page 10: ...y piping adjacent to the boiler outlet connection CAUTION Failure to properly install the flow switch may result in damage to the boiler water heater heat exchanger voiding the warranty HEATING SYSTEM...

Page 11: ...ow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop GPM Ft L s kPa GPM Ft L s kPa GPM Ft L s kPa GPM Ft L s kPa 4 0 4 3 4 7 5 0...

Page 12: ...ow Return Water Temperatures To prevent the problems associated with condensation of the products of combustion due to low return water temperatures a primary secondary piping system with a bypass and...

Page 13: ...guration and valving Check with local codes and ordinances for specific requirements Adjustment Procedure To Maintain Inlet Temperature Above Dew Point T1 Temp Min 110 For Atmospheric T1 Temp Min 125...

Page 14: ...s furnished with factory mounted outlet water temperature gauge 4 Boiler pump purging required Use terminals supplied 5 Secondary loop pipe diameter must be sized large enough to handle maximum flow t...

Page 15: ...tion of the pump size and temperature rise A cupro nickel heat exchanger may also be required The manufacturer should be consulted when these water conditions are encountered See Table 7A CAUTION The...

Page 16: ...elow can be employed to prevent this condition from occurring A balancing valve should be installed on the outlet side of the water heater for purposes of adjusting the flow rate through the heat exch...

Page 17: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 17 Table 7B 8900 Pumping Performance RequirementTable...

Page 18: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 18 Table 7B 8800 Pumping Performance RequirementTable...

Page 19: ...formance Table before making selection 6 Common piping must be sized for maximum combined heater flow 7 Hot water tanks should be equipped with a combination temperature pressure relief valve 8 MA Cod...

Page 20: ...type of gas available at the installation site call the nearest RBI representative to resolve the problem NOTE A minimum gas supply presssure of 6 in 152 mm W C natural or 11 in 279 mm W C propane and...

Page 21: ...diagram supplied with the boiler water heater for proper wiring connections GENERAL OPERATION WARNING Before proceeding read and fully understand the instructions contained in this manual Do not attem...

Page 22: ...n interrupteur ne pas vous servir des t l phones se trouvant dans le b timent Appelez imm diatement votre fournisseur de gaz depuis un voisin Suives les instructions du fournisseur Si vous ne pouvez r...

Page 23: ...reil ne se met pas en marche suivez les instructions intitul es Comment couper l admission de gaz de l appareil et appelez un technicien qualifi ou le fournisseur de gaz inches W C mm W C Natural 3 5...

Page 24: ...anifold pressure tap plug CAUTION Never force the regulator adjustment screw beyond the stop limits or damage to the regulator will occur PROPANE GAS Optimum results are obtained when the boiler water...

Page 25: ...water is 130 F 54 C The operating control should be set to the lowest setting that will satisfy the consumer s needs WARNING Setting the thermostat or operation control too high can result in scaldin...

Page 26: ...osion or other deposits that would impair the boiler water heater s performance Refer to page 30 8900 or page 39 8800 for component identification Combustion Chamber Inspection 1 Remove the left or ri...

Page 27: ...the GENERAL OPERATION and CHECKING AND ADJUSTMENTS sections of this manual for reference 1 Check the thermostat or operating controls for proper operation 2 A float type low water cutoff device must...

Page 28: ...ose or broken wire between pilot valve and PV MV PV terminals 24V at pilot gas valve leads Replace module Adjust the pilot gas pressure using the pilot regulator Pilot ignition problems can be caused...

Page 29: ...f valve is properly sized for the system never exceed 160 psi Expansion tank is waterlogged Ensure expansion tank is properly sized for the system Expansion tank is isolated Ensure valve between expan...

Page 30: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 30 PARTS LIST MODELS 420 1900 36 33...

Page 31: ...0113 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 RH Lower Front Corner Post 03 0114 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 5 24 Jacket End Panels Upper Lower 72 0016 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 6 Inlet Outlet Header Cast...

Page 32: ...0 0277 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 Burner Tube w Bracket 70 0635 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 NS Burner Spacers 03 0309 1 03 0310 1 03 0311 1 03 0312 1 03 0313 1 03 0314 1 03 0315 1 03...

Page 33: ...1 NS Bracket Refractory Upper End 03 0306 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 NS Bracket Refractory Lower End 03 0307 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 18 End Refractory Panel Left Right 05 0001 2 2 2 2 2 2 2...

Page 34: ...70 0189 1 70 0190 1 70 0191 1 NS Upper Rear Refractory Channel 70 0162 1 70 0163 1 70 0164 1 70 0165 1 70 0166 1 70 0167 1 70 0168 1 70 0169 1 70 0170 1 70 0171 1 70 0172 1 70 0173 1 70 0174 1 70 0175...

Page 35: ...0057 1 27 Jacket Top Panel 03 0001 1 03 0002 1 03 0003 1 03 0004 1 03 0005 1 03 0006 1 03 0007 1 03 0008 1 03 0009 1 03 0010 1 03 0011 1 03 0012 1 03 0013 1 03 0014 1 03 0015 1 27a Jacket Top Panel Du...

Page 36: ...Heat Exchanger Assembly Cupronickel 70 0087 1 Cast Iron Headers 70 0088 1 70 0089 1 70 0090 1 70 0091 1 70 0092 1 70 0093 1 70 0094 1 70 0095 1 70 0096 1 70 0097 1 70 0098 1 70 0099 1 70 0100 1 70 01...

Page 37: ...or LP 24V 11 0375 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Solenoid Valve w Regulator NG 120V 11 0372 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Solenoid Valve w Regulator LP 120V 11 0374 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 35 Man...

Page 38: ...G 10 0019 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 Orifice 47 LP 10 0009 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 Orifice 49 2 000 3 999 LP 10 0010 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 Or...

Page 39: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 39 PARTS LIST MODELS 2000 4000 22 7 36 33 30 8 6 39 42 18 21 25 19 21a...

Page 40: ...et Return Headers ASME 57 0492 24 24 24 24 24 24 NS Heat Exchanger V Baffle 03 1147 15 03 1148 30 03 1149 30 03 1150 30 03 1151 30 03 1152 30 12 Base Frame Assembly 70 1708 1 70 1709 1 70 1710 1 70 17...

Page 41: ...Only 11 0455 1 1 18 End Refractory Panel Left Right 05 0050 2 2 2 2 2 2 19 Center Refractory Panel 853413 4 4 6 8 8 10 20 Corner Refractory Panel 05 0052 4 05 0053 4 05 0054 4 05 0055 4 05 0056 4 05 0...

Page 42: ...4V 70 9013 1 1 1 1 1 1 Ignitor PSE NA185 NG 120V 70 9014 1 1 1 1 1 1 Ignitor PSE NA29 LP 24V 70 0631 1 1 1 1 1 1 Ignitor PSE NA185 LP 120V 70 0632 1 1 1 1 1 1 33 Solenoid Valve w Regulator NG 24V 11 0...

Page 43: ...0007 20 24 28 32 36 40 Orifice 22 4 000 5 999 NG 10 0095 20 24 28 32 36 40 Orifice 25 6 000 7 999 NG 10 0097 20 24 28 32 36 40 Orifice 34 LP 10 0021 20 24 28 32 36 40 Orifice 37 2 000 3 999 LP 10 002...

Page 44: ...the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next ad...

Page 45: ...led instructions for the installation of the venting system design or the venting system components and 2 A complete parts list for the venting system design or venting system d MANUFACTURER REQUIREME...

Page 46: ...nd erosion on the inside of the heat exchanger tubes caused by high water velocity through the tubes and is not covered by the manufacturer s warranty See Installation Instructions for proper pump per...

Page 47: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 47...

Page 48: ...260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782...

Reviews: