UNC100 Integra Manual
New Generation Building Security
July 30, 2014 – V1.2
Page 1: ...UNC100 Integra Manual New Generation Building Security July 30 2014 V1 2 ...
Page 2: ... product names mentioned herein are the property of their respective owners Use of a term in this book should not be regarded as affecting the validity of any trademark or service mark Disclaimer This book is provided as is without warranty of any kind either express or implied including but not limited to performance merchantability or fitness for any particular purpose Neither RBH Access Technol...
Page 3: ...erence to rack mount type Clarified the use of the Power Input Output Moved all cable specs to one location Moved all input specs to one location Moved all output specs to one location Reduced the number of pages 03 19 14 DM 1 1 Minor editing of text 03 24 14 RB 1 2 Changing output voltage from 12V to 12v 14v Changing battery charger spec 07 21 14 DM 1 2 Editing of text Changed graphic Removed rel...
Page 4: ...gnostic LED s 7 Tamper Detection 7 Power Input Output 8 Communication 8 Networks 8 RS485 Applications 8 DIP Switch Settings 8 Controller Addressing 9 RS485 HOST Port Baud Rate Selection 10 Host Connection 11 PC to UNC100 Connection RS485 Wiring 11 UNC100 TCP IP Connection 12 Reader Interface 14 Reader Connection 14 Outputs 15 Switching Inductive Devices Locks Bells 15 Output Operation 16 General P...
Page 5: ...ons 18 Request to Exit RTE 19 Door Contact DC 19 General Purpose 19 Access Point Operating Modes 19 High Security 19 Unlocked 19 Tamper 19 Lockout Alarm 19 Door Held Open Warning 19 Door Held Open Alarm 19 Keypad Reader Combination 19 Access Granted 19 Access Denied 19 UNC100 Specification 20 Cable Specification 20 ...
Page 6: ...UNC100 Axiom Hardware Manual V1 2 RBH Access Technologies Inc Page 6 of 20 Panel Graphics ...
Page 7: ...d or scheduled When initiated the charger is turned off and a 24Ω resistor provides a load to the battery for about ten seconds If during this period the voltage drops below 10 volts a battery alarm message is sent to the host otherwise a battery normal message is sent Fuse Monitoring Besides monitoring the battery voltage the UNC100 also monitors the input voltage DC auxiliary voltage aux and the...
Page 8: ... channel may be programmed as either NONE or INTEGRA Use the DIP switch to select baud rate for Host communications as 9600 38400 57600 or 115200 Networks There are two networks supported by the UNC100 these are 1 Host Communications through the Ethernet or direct connection 2 Integra Communications for devices such as additional IRC 2000s or URC 2000s starting at address 2 and PC100s RS485 Applic...
Page 9: ...tch settings for all fifteen possible addresses are given below Controller Addressing Switch 1 Switch 2 Switch 3 Switch 4 Address Off Off Off Off Clear Memory On Off Off Off 1 Off On Off Off 2 On On Off Off 3 Off Off On Off 4 On Off On Off 5 Off On On Off 6 On On On Off 7 Off Off Off On 8 On Off Off On 9 Off On Off On 10 On On Off On 11 Off Off On On 12 On Off On On 13 Off On On On 14 On On On On ...
Page 10: ...t with controller DIP switches 6 and 7 This setting determines the speed used to communicate with the PC the controller baud rate must be the same as the baud rate set for the port within the Integra software The default baud rate is 9600 Controller Baud Rate Selection DIP Switch 6 DIP Switch 7 Baud Rate OFF OFF 9600 ON OFF 38400 OFF ON 57600 ON ON 115200 ...
Page 11: ...he means of communication is configured in the Integra software under the network s properties under the Comms tab PC to UNC100 Connection RS485 Wiring Cable Specification Twisted pair shielded 18 to 22 AWG Maximum Cable Length 2000 4000 feet 600 1200 meters For ULC S319 05 III compliance all wiring into the panel s cabinet must enter through metal conduit Also be sure to mount the panel in a prot...
Page 12: ...inked by the local Ethernet The system supports a static IP address only default address is 192 168 168 125 To change the IP address of the unit you can either use IP Locator a utility program provided by RBH or Telnet PC to UNC100 Connection LAN For ULC S319 05 III compliance all wiring into the panel s cabinet must enter through metal conduit Also be sure to mount the panel in a protected area ...
Page 13: ...mary port number ALT PORT NUMBER 3003 Alternate port number applies to LAN application RS485 INTEGRA Set the RS485 to INTEGRA in order to connect via RS485 to the PC and other Integra devices Telnet Password password This is a string of up to 10 characters that allows the user access to this program Integra Network URC2000 panels may also be used in place of IRC 2000 panels When UNC100 panels are ...
Page 14: ... be ignored but once a short is connected it will report a reader tamper alarm whenever the input is opened LED and beeper outputs are open collector current limited to 100ma Reader Connection RC 2 to 12 Volt Reader Connection Diagram1 For ULC S319 05 III compliance all wiring into the panel s cabinet must enter through metal conduit Also be sure to mount the panel in a protected area 1 Reader wir...
Page 15: ...or 100ma 3 Lock Reader 2 Relay form C 4 Forced Entry Alarm Reader 2 Open Collector 100ma Switching Inductive Devices Locks Bells Exercise caution when switching an inductive load Inductive devices include external relay solenoids bells and door locks All of these devices generate extremely high voltage spikes several thousand volts when applied power is removed Possible disruption of operation cou...
Page 16: ...output is used to drive door operators It turns on in less than one second after the Lock Output is turned on and stays on until the Lock Output is turned off Only designated cardholders will activate this output Forced Tamper The Forced Tamper output turns on if the door is forced open or if a reader tamper is detected This output remains on for as long as the alarm condition exists Modem Power O...
Page 17: ...2k represents an alarm state If the loop resistance changes by more than 15 but not enough to enter the next state an illegal state is reported Input Circuit Types The UNC 100 supports seven different input circuit types ranging from no resistor for low security applications to two resistor normally closed circuits where the highest security is required Normally Closed No Resistor Loop Resistance ...
Page 18: ... used in the same loop Input Applications Number Default Application 1 General Purpose 2 RTE Request to Exit Reader A 3 DC Door Contact Reader A 4 RTE Request to Exit Reader B 5 DC Door Contact Reader B Normally Open One Resistor Loop Resistance State Short Alarm 1k Restore Open Circuit Trouble Normally Open Two Resistor Loop Resistance State Short Trouble 1k Alarm 2k Restore Open Circuit Trouble ...
Page 19: ...High Security Mode only cardholders with High Security Privilege are allowed access Unlocked The green LED turns on to indicate the door is unlocked Tamper The Buzzer sounds continuously Lockout Alarm The Buzzer beeps rapidly A lockout alarm occurs when a user defined number of Access Denied messages occur These messages can include Invalid Card Number No Access at this Time No Access at this Read...
Page 20: ...Time Clock Built in as standard Watch Dog Circuit Built in as standard Board Dimensions H 5 in x W 5 in 14 x 12 cm Operating Temperature 0 to 70C 35 150F Operating Humidity 20 to 85 RH non condensing Cable Specification Circuit Function Cable type Length PC To Controller Ethernet CAT5 communications cable 323 feet 100 meters PC To Controller RS485 Twisted pair shielded stranded 18 to 22 AWG 2000 4...