24
7.5
Trigger input options
The trigger sense and the way the VCT6 is triggered can be changed
according to how you set the 'P' flag. This is summarised in the table below:
Mode
Trigger input
Output
Switched
Input = off
Is
off
if P Flag =
1
Is
on
if P-Flag =
0
Input = on
Is
on
if P Flag =
1
Is
off
if P-Flag =
0
Pulsed
Trigger rising edge
Pulse is triggered
if P-Flag =
1
Trigger falling edge
Pulse is triggered
if P-Flag =
0
The 'P' flag can be set from the VCT6's web pages (see Section 9, Webpage
configuration), or through its command interface (see Section 10,
Configuration commands).
7.6
Factory settings
The default configurations for the VCT6 light output and trigger output are as
listed below:
Pulse operation
1ms pulse width
20.0μs
pulse delay
100% intensity
32.26ms re-trigger delay, for 850nm variants, and 100.0ms retrigger delay for
white variants.
The
CL
command can be used to restore the VCT6 to its default
configuration.