24
Raypak, Inc.
confIGuratIon
Button:
MENU/<Maintenance>/<Configuration>
• This menu option provides a consolidated view of the Startup and Stage settings.
dIsplay
The TempTracker mod+ display layout provides a variety of information that gives an
immediate picture of the operation status. The display shows four boilers at a time. The two
middle buttons scrolls the screen to view additional boilers. Moreover, all the information is
brightly displayed. It can be viewed in brightly or dimly lit rooms.
• The buttons' functionality changes based on the screen and menu level your in. The buttons'
functionality are displayed on a dark background on the screen bottom line.
• Horizontal arrows are to scroll through the available stages.
----------- SETTINGS ------------
Season
Winter
Set Point
70 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK
SAVE
---------------- GAIN --------------
+0
F
[
]
BACK SELECT
---------- SETTINGS 1 ----------
Gain
+0
Lead Rotation
Last-On
Purge Delay
1.0min
Lag Delay
0min
<More Settings>
BACK SELECT
---------- SETTINGS 2 ----------
Standby Time
7min
System Run-On
10min
Setback
10 F
Last Stage Hold
5 F
Set Time
12:05Pm
<Day/Night Schedules>
BACK SELECT
--- DAY/NIGHT SCHEDULES ---
Set Time
**:**
Day Schedule
**:**
Night Schedule
**:**
BACK
SAVE
---- MANUAL LEAD STAGE ----
A
B
C
D
E
BACK
SAVE
--- AUTO ROTATE PERIOD ---
24
hrs
[
]
BACK
SAVE
--------- PURGE DELAY ---------
1.0
min
[
]
BACK
SAVE
----------- LAG DELAY -----------
0
min
[
]
SYSTEM SETTINGS1
SYSTEM SETTINGS2
BACK
SAVE
-------- STANDBY DELAY --------
7
min
[
]
BACK
SAVE
-------- SYSTEM RUN-ON --------
10
min
[
]
BACK
SAVE
-------------- SETBACK -----------
10
F
[
]
BACK
SAVE
------ LAST STAGE HOLD ------
5
F
[
]
BACK
SAVE
----- SET PRESENT TIME -----
11:**Pm
SETBACK INPUT
Shutdown
/TStat
BACK SELECT
---------- MAINTENANCE ---------
System Trim
+0 F
Outdoor Trim
+0 F
Soft-Off Delay
10sec
<Output Trim>
<Configuration>
MAINTENANCE
BACK
SAVE
--- SYSTEM SENSOR TRIM ----
+0
F
[
]
BACK
SAVE
-- OUTDOOR SENSOR TRIM ----
+0
F
[
]
BACK
SAVE
------- SOFT-OFF DELAY --------
10
sec
[
]
BACK SELECT
-------- STAGE A TRIM --------
Output Trim
+0.0
<Prev Stage>
<Next Stage>
BACK
SAVE
-------------- STAGE A -----------
OUTPUT TRIM
+0.0
[
]
BACK
EXIT
------ CONFIGURATION 2 ------
A=4-20ma
B=0-10v
C=0-5v
D=2-10v
BACK
NEXT
------ CONFIGURATION 1 ------
v1.00c
Reset F
Parallel
Day/Night Schedules
All Off
BACK
SAVE
-------- LEAD ROTATION -------
Manual
Time
Last-On
• Vertical arrows are to scroll through the menu functions when
in menus or to change values of settings when in its specific
screen.
• The Top line displays the available sensor values.
• The second line displays the Target set point. However, it will
display any messages pertaining to the operation or status.
• The third line will list the boiler stages. Any additional stages
can be scrolled to using the two middle buttons. The Lead
boiler letter will be bracketed. See Lead Boiler Operation on
page 19.
• The fourth line lists each boiler modulation status. See Display
Boiler Modulation Status for possible status.
140
F
A B C D
50% 15% --- ---
STAGE
ÿÿÿÿÿÿÿÿÿÿÿÿ
MENU
SET POINT
OD=
35
F SYS=
98
F
Prepurge Delay:67
A B C D
50% 15% --- ---
STAGE
ÿÿÿÿÿÿÿÿÿÿÿÿ
MENU
Outdoor Temp
System Temp
Message Display Line
Boilers and their
Modulation Status
Button functions
Button
dIsplay boIler ModulatIon status
The TempTracker mod+ boiler modulation status gives immediate access to each boiler status. The following list show all possible
boiler status:
• ---
Boiler is off due to no call for heat.
• 97%
Boiler is modulating at the indicated percentage.
• ON
Boiler Stage Mode is set to ON and boiler is firing at 100% (boiler is in bypass).
• OFF
Boiler Stage Mode is set to OFF and boiler stage is unavailable or boiler does not exist.
• m95%
Boiler Stage Mode is set to Manual and set to the specified percent.
• h50%
Boiler is in post purge for 30 seconds.
• C/E
Boiler on Extension panel is communicating back to the TempTracker mod+..
dIsplay MessaGes
The TempTracker mod+ normal display layout reserved the second line for message indications. The following is a list of the most
common Message Display Line information:
• Summer
The control is set to Summer. No heat is active.
• Shutdown Active
The Shutdown Terminals are Shorted. No boilers will be active.
• Shutdown by EMS The EMS is below 2mA or above 22mA. See EMS input page 14.
• Tstat Call
The Tstat Terminals are Shorted. Boilers will be active.
• DHW Call (171˚F) There is a DHW (Domestic Hot Water) call. The TempTracker mod+
will Raise the system Set Point to the
indicated temperature. DHW increases calculated temperature to the DHW Set Point (see page 15).
• Purge Delay: 23
The current boiler is in purge cycle and the remaining purge time in seconds is 23.
• Lag Delay: 123
The lead boiler is at 100% and the remaining purge time to start the lag boiler in seconds is 123. See Lag
• Holding Until 150˚F The Lead boiler is in Last Stage Hold. This example shows that the lead stage will turn off when system
temperature reaches 150˚F.
• System Run-On: 46 The System relay is ON for the System Run-On Delay. This example shows that it will remain in System
Run-On for an additional 46 seconds before turning off.
• Waiting for Prove
The System relay is ON and the prove terminals are open before the lead boiler relay can energize. See
• Prove Failure
After boilers have run for a while, Prove signal was opened. The boiler relays will de-energize. However,
the System relay will remain energized. See Prove setting on page 15.