16
Raypak, Inc.
sensor fault
All Off, All On
Default: All On
Button: MENU/<System Startup>/..../Sensor Fault
The Sensor Fault will determine the operating status of all output stages that are set to Auto
when a sensor reads Short or Open.
----------- SETTINGS ------------
Season
Winter
Set Point
140 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK
SELECT
BACK
SAVE
------------- SEASON --------------
Winter
Summer
BACK
SAVE
------------ SET POINT ----------
140
F
[
]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK
SAVE
BACK
START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK
CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK
SAVE
------- OUTDOOR CUTOFF -------
65
F
[
]
-------------- OFFSET -------------
+0
F
[
]
BACK
SAVE
--- MINIMUM WATER TEMP ----
140
F
[
]
BACK
SAVE
--- MAXIMUM WATER TEMP ----
220
F
[
]
Reset Ratio
BACK
SAVE
Shutdown or TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120
F
[
]
------ EMS 20ma SETPOINT-----
220
F
[
]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK
SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK
SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK
SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK
SAVE
BACK
SAVE
BACK
SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
BACK
SAVE
BACK
SAVE
BACK
EXIT
BACK
NEXT
BACK
SAVE
BACK
SAVE
Enabled
BACK
SAVE
------- DHW SETPOINT -------
180
F
[
]
Disabled
reset Mode
• When All-On is selected, the TempTracker mod+ will turn all boilers On to a 100% when System reads Short or Open and Outdoor
is below Outdoor Cutoff. When Outdoor reads Short or Open, the TempTracker mod+ will turn all boilers On to a 100%.
• When All-Off is selected, the TempTracker mod+ will turn all boilers Off when either System or Outdoor sensor reads Short or
Open.
set poInt Mode
• When All-On is selected, the TempTracker mod+ will turn all boilers On to a 100% when the System sensor reads Short or Open.
• When All-Off is selected, the TempTracker mod+ will turn all boilers Off when the System sensor reads Short or Open.
• The Outdoor Sensor Short or Open status will not affect the control operation in Set Point mode.
settInG tHe control to factory defaults
To Reset the TempTracker mod+ control to its original factory defaults, power down the
control. Hold down the two right most buttons while powering the control back up until the
Total Clear Started
screen appears. The Display will direct you to the Startup
menu to program the control after the defaults are loaded.
TOTAL CLEAR STARTED
Release buttons
and
Please Wait
NOTE: When resetting the control to original factory defaults all control settings will be overwritten and will no longer exist.
alert
Do not turn off power to control until all Startup settings have been made. Otherwise, the next
power-up will be set to many Startup factory settings that might not fit your application.