48
Raypak, Inc.
HTC# 059105-00D
st
a
GI
n
G
-
set
po
Int - B
ac
net V
ar
Ia
B
le l
Ist
Hybrid
r
eset
o
bject I
d
o
bject
type
o
bject
n
ame
u
nits
Value
d
efinition
Min
Max
Model
Device Object
MODEL
Serial Number
Device Object
SNUMBER
Version
Device Object
VERSION
Operation Mode
100
MUL
TIST
ATE-V
ALUE
OPMODE
1
6
1=Modulation Reset, 2= Staging Reset, 3=Hybrid Reset, 4=Modulation Setpoint, 5=Staging Setpoint, 6=Hybrid EMS
Outdoor
Temperature
200
ANALOG-V
ALUE
ODTEMP
Degree F
32000=OPEN,3201=SHOR
T
System
Temperature
300
ANALOG-V
ALUE
SYSSEN
Degree F
32000=OPEN,3201=SHOR
T
Output Status
400
ANALOG-V
ALUE
OPTST
AT
0
0x1FFFF
Each Bit represents one of the possible 16 relays. Bit 0 represents Relay1, Bit 16 represents Relay16. 0 = Relay OFF
, 1 = Relay ON
Control Status
500
MUL
TIST
ATE-V
ALUE
CST
AT
1
13
1=SHUTDOWN,2=NO
TST
AT
CALL,3=PROVE F
AILURE,4=SHUTDOWN
BY
EMS,5=W
AITING FOR PROVE,6=SENSOR F
AUL
T,7=LAST
ST
AGE
HOLD,8=DHW CALL,9=SUMMER,10=BOOST
MODE,1
1=SYSTEM
RUNON,12=SETBACK MODE,13=OUTDOOR CUT
OFF
Season
600
MUL
TIST
ATE-V
ALUE
SEA
1
2
1= Winter
, 2= Summer
Setpoint
700
ANALOG-V
ALUE
SETP
Degree F
70
250
Integer V
alues Only (70,71,72…)
Outdoor Cutof
f
800
ANALOG-V
ALUE
CO
Degree F
19
101
Integer V
alues Only (19,20,21…)
Setback
900
ANALOG-V
ALUE
SB
Degree F
0
75
Integer V
alues Only (1,2,3…)
Purge Delay
1000
ANALOG-V
ALUE
PDL
Y
Minutes
.1
10
.1 thru .9 after Integer V
alues Only (1,2,3…)
System Runon
1100
ANALOG-V
ALUE
RUNON
Minutes
0
360
Integer V
alues Only (0,1,2…)
Rotation
Time
1200
ANALOG-V
ALUE
R
TTIME
Hours
1
1440
Hours since last rotation Integer V
alues Only (1,2,3…)
Standby
Time
1300
ANALOG-V
ALUE
STBYDL
Y
Minutes
1
60
Integer V
alues Only (1,2,3…)
Last Stage Hold
1400
ANALOG-V
ALUE
LSTHOLD
Degree F
0
30
Integer V
alues Only (0,1,2…)
Con Lead Stage
1500
MUL
TIST
ATE-V
ALUE
CLEAD
1
16
Represent the current lead boiler for the condensing group
Non-Con Lead Stage
1600
MUL
TIST
ATE-V
ALUE
NCLEAD
1
16
Represent the current lead boiler for the non-condensing group
Reaction
Time
1700
ANALOG-V
ALUE
RETIME
Minutes
1
10
Integer V
alues Only (1,2,3…)
Min Run
Time
1800
ANALOG-V
ALUE
MINRUN
Minutes
1
60
Integer V
alues Only (1,2,3…)
Set
Time
1900
ANALOG-V
ALUE
PTIME
Minutes
1
1440
Time since midnight Integer V
alues Only (1,2,3…)
Day Schedule
2000
ANALOG-V
ALUE
DSCHED
Minutes
1
1440
Time since midnight Integer V
alues Only (1,2,3…)
Night Schedule
2100
ANALOG-V
ALUE
NSCHED
Minutes
1
1440
Time since midnight Integer V
alues Only (1,2,3…)