TempTracker mod+ Hybrid Installation and Operation Manual
27
HTC# 059105-00D
Bacnet Mstp startup Menu
-------- SETTINGS ----
Season
Winter
System Target 140
o
F
<System Settings>
<Maintenance>
<System Startup>
BACK
▲
▼
SELECT
-- ARE YOU SURE? --
No
Yes
BACK
▲
▼
SAVE
--- BACNET MODE ---
Disable
Enable
BACK
▲
▼
SAVE
- BACNET BAUDRATE -
9600
19200
38400
BACK
▲
▼
SAVE
----MS/TP ADDRESS----
64
[ ]
BACK
▲
▼
SAVE
---- BACNET ID ----
477000
[
]
BACK
▲
▼
SAVE
When using the TempTracker mod+ Hybrid in a BACnet MS/TP network, the use of BACnet Interface Module is required (#651735).
In addition, each of the Boiler Type and Sensor Type Startup menu option will offer a different list of BACnet variables. See "Boiler
Type" on page 20. See "Sensor Type" on page 20. Also, see "Hybrid - Outdoor Reset - BACnet Variable list" on page 44
Bacnet Mode
Enable, Disable
Default: Disable
Button:
MENU/<System Startup>/.... Sensor Fault/BACnet Mode
• This menu option enables or disables the BACnet MSTP capability. When enabled,
additional BACnet settings shall be available for further customizing.
• Note that if this option was enabled while no BACnet communication is present, the BAcnet
error message will supersede other messages. See "Display Messages" on page 40.
--- BACNET MODE ---
Disable
Enable
BACK
▲
▼
SAVE
Bacnet Baud rate
9600, 19200, 38400
Default: 19200
Button:
MENU/<System Startup>/.... Sensor Fault/BACnet Mode/BACnet Baudrate
• For the control to communicate over a BAcnet MS/TP network, it must use the same Baud
rate as the rest of the network. The control offers three Baud Rates.
• If communication was not successful, the baud rate could be the cause. Check with the
network administrator for the network baud rate. Then match it on the control.
- BACNET BAUDRATE -
9600
19200
38400
BACK
▲
▼
SAVE
Ms/tp address
1 to 127
Default: 64
Button:
MENU/<System Startup>/.... /BACnet Mode/BACnet Baudrate/ MSTP Address
• Each device on the MS/TP network must have a unique address.
• This is the MS/TP address on a RS485 network. Its MS/TP range is 1 though 127.
• The MS/TP address must be provided by the Network Administrator.
----MS/TP ADDRESS----
64
[ ]
BACK
▲
▼
SAVE
Bacnet Id
1 to 4,000,000
Default: 477,000
Button:
MENU/<System Startup>/.... / MSTP Address / BACnet ID
• The BACnet ID is a unique 32 bit number that identifies the control within the BACnet
network. No two ID shall be the same even if dealing across networks.
• It must be provided by the BACnet Network Administrator.
---- BACNET ID ----
477000
[
]
BACK
▲
▼
SAVE