background image

Catalog No.:  3500.24B 

Effective:  1-15-08 

Replaces:  7-15-04

 

Job:  

         

 

 

 

Engineer:  

         

 

 

Contractor:  

         

 

 

Prepared By:  

         

 

 

 

Model:   

           

Indoor Date:

            

 

 

 

EFFICIENT 

 

82% thermal efficiency – highest of any atmospheric 
water heater available today 

THERMAL SHOCK PROOF 

 

Twenty-year warranty against thermal shock damage 
up to 150°F differential 

 

Maximum operating temperature: 210°F 

LIGHTWEIGHT 

 

A floor load of 70 lbs./sq. ft. or less 

HIGH RECOVERY 

 

Cuts fuel costs substantially because the standby  
and radiation losses associated with tank-type  
water heaters are eliminated 

LOW WATER OPERATING TEMPERATURE 

 

Operates with water temperature as low as 105°F 
without condensing 

 

Heat Exchanger 

ƒ

  ASME Inspected and Stamped 

160 PSIG 

ƒ

  National Board Approved 

ƒ

 Headers 

 Bronze – Standard  
 Glass-lined Cast Iron – Option A-2 

ƒ

 Fin 

Tubing 

 Copper – Standard 
 Cupro Nickel – Option A-3 

ƒ

  ASME Steel Tube Sheet 

ƒ

 Silicone 

O-Rings 

ƒ

  125 PSIG ASME Pressure Relief Valve 

ƒ

  Temperature and Pressure Gauge 

ƒ

 Water 

Connections 

 Left Hand – Standard  
 Right Hand – Option A-6 

ƒ

  Two-pass Flow Configuration 

Controls 

ƒ

  120V, 60Hz, 1 Ph Power Supply 

ƒ

 120/24V 

Transformer 

ƒ

  100% Pilot Shut-off/Lockout 

ƒ

 Electronic, 

Intermittent Ignition (IID) Pilot 

ƒ

  High Limit Control, Manual Reset – 200°F  

ƒ

  High Limit Control, Auto Reset – 200°F 

Models 3001-4001 

ƒ

 On/Off 

Switch 

ƒ

 Flow 

Switch 

ƒ

  Economaster II Pump Time Delay 

Gas Control Train 

ƒ

  Manual Main Gas Shut-off Cock 

ƒ

  Main Gas Pressure Regulator 

ƒ

  Redundant Safety Shut-off Valve 

ƒ

  Control Valve         

ƒ

 Firing 

Mode 

 On/Off (WH1) 
 2-stage Firing (WH3) 
 Motorized Modulation (WH2) 

ƒ

 Fuel 

 Natural Gas 
 Propane Gas     

ƒ

  Design Certified ANSI Z21.10.3 

Construction 

ƒ

 Front 

Controls 

ƒ

  Stainless Steel Burners 

ƒ

  Baked Enamel Paint 

ƒ

  Built-in Draft Diverter 

ƒ

  Draft Inducer – Optional 

 Motorized Draft Inducer –  

Indoor – Option D-2 

Water Heater Controller 

Required on Model WH2 only

 

 B-17  Modulating Controller 

(104-220°F), Mounted 

  

By Others 

Temperature Controllers 

 B-2 

Single-Stage Tankstat  
(100-180°F), Loose 

 B-3 

2-Stage Tankstat (100-180°F), 
Loose 

 Y-241 Electronic Sequencer,  

1-4 Stages 

 Y-281 Electronic Sequencer,  

1-8 Stages 

Additional Safety Controls 

 F-9 

Low Water Cut-off Probe 

 I-3 

High Limit Control, Auto Reset, 
180°F 

 S-1 

Low Gas Pressure Switch, 
Manual 

 S-2 

High Gas Pressure Switch, 
Manual 

                       

 

                       

 

Regulatory Agency Requirements 

 CSD-1 

Safety 

Controls 

 

             

 

Raytherm

®

 

- Type WH

Water Heaters

Commercial

Models 2100 - 4001

INDOOR 