background image

12

4.  ELECTRICAL WIRING

Wiring

Electrical  installation  should  be  done  by  a  licensed 

electrician only.

1. 

Confirm the power supply is at the rated voltage of 

the appliance and make the connection. 

2. 

Ground the heater.

3.  Wiring must be installed by a professional installation 

technician and follow the circuit diagram. 

Electrical Connections

Electrical  installation  should  be  done  by  a  licensed 

electrician only. 
Refer to the unit rating plate below the control panel for 

precise power requirements for your unit, and for ampacity 

and over-current protection requirements.
All wiring must be in accordance with the National Electrical 

Code, NFPA No. 70, latest edition, and all applicable state 

and local codes. The wiring diagrams are located on page 

13 through page 16.

A

A

WARNING:

  This  heater  MUST  be  installed  using 

flexible  conduit  for  supply  wiring  to  the  unit.  This  will 

allow  movement  of  the  conduit  whenever  the  junction 

box is removed for service.

Locate  the  equipment  disconnect  means  within  3  ft. 

(0.9  m) of the heater’s electrical enclosure, or as close to 

the heater as possible. Always satisfy applicable codes 

and standards.
In sizing power wiring, be especially aware of up-sizing 

requirements necessary due to wiring distances. Always 

satisfy applicable codes and standards.

NOTE:

  Refer  to  the  National  Electrical  Code,  Article 

680, for general requirements for swimming pools and 

equipment, and to Article 440 for special considerations 

necessary for circuits supplying hermetic refrigeration 

motor/compressors.

This  heater  is  pre-wired  to  work  with  external  control 

systems, heat-on-demand options and other external time 

clock  overrides.  Refer  to  the  external  control  system’s 

instructions.

Models

Power

Min. 

Circuit

Ampacity

Breaker Size 

(Amp)

min. max.

CROSSWIND-30-I

208-230VAC

 

60HZ/1PH

12A

15A

15A

CROSSWIND-40-I

16A

20A

20A

CROSSWIND-50-I

17.2A

20A

25A

CROSSWIND-65-I

12A

15A

15A

CROSSWIND-40-O

12A

15A

15A

CROSSWIND-50-O

16A

20A

20A

CROSSWIND-65-O

20A

20A

25A

* Reference only - see National Electric Code or local codes for wire gauge length 

limits.

Table D.  Electrical Power Requirements

Automation Control, 

Inverter Models Only

2-Wire System - Heat Only

The Crosswind inverter models have temperatures sensor 

for temperature automation control.
Heater 2-Wire Controllers (Heat Only)

1. 

Install wires from the automation controller for “Heat” 

on  the  terminal  strip  inside  the  heater  electrical 

compartment on the side of the heater.

2. 

Remove the jumper wire on the terminal block from 

terminals  marked  #5  and  #6.  See 

Figure  11, 

and 

wiring diagrams on

 page 15 

and

 page 16

.

L

1

L

2

P

1

P

2

5   6

PUMP CONTROL

POWER

208 -230V/60HZ 

CUSTOMER REMOTE

CONTROL SWITCH

CONNECTOR

YLW/GRN

Figure 11.  Automation Control 2-Wire System Connection

3.  Install  the  automation  control  wires  for  “Heat”  to 

terminals #5 and #6.

4. 

Set  temperature  setting  on  the  heater  to  104°F 

(40°C).

NOTE:

  When  the  automation  controller  has  a 

HEAT  command  the  unit  will  be  in  the  HEAT  mode. 

 

When the automation controller does not have a HEAT 

command the unit will be in the OFF mode.

6100.64_Crosswind.indd   12

11/26/2019   4:16:43 PM

Summary of Contents for CROSSWIND Series

Page 1: ...he use of qualified individuals specially trained and experienced in the installation and maintenance of this type of equipment and related system components Installation and service personnel are required by some states to be licensed Persons not qualified shall not attempt to install service or maintain this equipment This manual should be maintained in legible condition and kept adjacent to the...

Page 2: ...l of the above information in hand please contact us and ask to register your brand new heat pump or do it online at http warranty raypak com 800 260 2758 M F 8 30 4 30 EST You will be given a Warranty Registration Confirmation number which you should notate and keep in one location along with your Installation and Operation Manual a copy of your warranty provided with your manual and the above in...

Page 3: ...r Models Only 12 5 WIRING DIAGRAM 13 Crosswinds 30 I 40 I 50 I 13 Crosswinds 65 I 14 Crosswinds 30 O 40 O 15 Crosswinds 50 O 16 6 CONTROLS 17 Inverter Models Only 17 On Off Models Only 18 Using the On Off Display Unit 18 7 OPERATING INSTRUCTIONS 19 Start Up Procedures 19 Before Start Up 19 Starting 19 After Start Up 19 Maintenance 20 Cold Weather Operation 20 Testing 20 8 TROUBLESHOOTING 21 Fault ...

Page 4: ...t incorporates a pressurized refrigerant gas in a sealed system ONLY trained and qualified service personnel are authorized to install or service this equipment Without proper training and knowledge of such equipment any attempt to install or service the unit could result in serious injury or even death A ACAUTION Please do not place hands into the outlet of the swimming pool heater and do not rem...

Page 5: ...he case and performing service work 1 The heater must be installed by a qualified electrician 2 Set heating temperature within the recommended range to maximize comfort 3 Keep the air inlet and exhaust free from obstructions 4 This heater has a power off memory function 5 When the ambient temperature is at or below 32 F 0 C make sure the main power switch is turned off and all water is drained fro...

Page 6: ...l keep evaporation the main cause of main heat loss to a minimum and will greatly reduce pool heating costs During warmer weather the cover may be required only at night INSTALLATION Installation Considerations Locate the heater carefully to minimize installation costs while providing maximum efficiency of operation and to allow adequate service access as follows For unrestricted air intake and se...

Page 7: ...VERTICAL CLEARANCE 12 305 mm MINIMUM 12 305 mm MINIMUM 12 305 mm MINIMUM 12 305 mm MINIMUM F10762 Figure 2 Ventilation Clearances 3 Do not stack anything that will block air flow near the inlet or outlet areas or have any barrier within 20 in 508 mm behind the main heater or the efficiency of the heater will be reduced 4 The heater needs a pool pump to be supplied by the user For recommended pump ...

Page 8: ...EIN A LICENSED ENGINEER OR REGISTERED ARCHITECT SHALL PREPARE SITE SPECIFIC DOCUMENTS FOR USE IN CONJUNCTION WITH THIS DOCUMENT SITE SPECIFIC PRESSURE REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH ASCE 7 10 AND CHAPTER 16 OF THE FLORIDA BUILDING CODE SHALL BE LESS THAN OR EQUAL TO THE DESIGN PRESSURE CAPACITY VALUES LISTED HEREIN FOR ANY ASSEMBLY AS SHOWN DESIGN PRESSURE REQUIREMENTS SHALL BE DETE...

Page 9: ... HEAT EXCHANGER WATER INLET 1 1 2 PVC UNION LED CONTROLLER WATER OUTLET 1 1 2 PVC UNION Figure 6 On Off Model Component Locations Front View Figure 7 On Off Model Component Locations Right Side View Inverter Models 60Hz Heating and Cooling Models Unit Size BTUH Raypak P N Rheem P N RUUD P N Jacuzzi P N CROSSWIND 30 I 30k 17738 17742 17746 17750 CROSSWIND 40 I 40k 17739 17743 17747 17751 CROSSWIND ...

Page 10: ...2 48 CROSSWIND 50 I 079716 12 40 315 23 22 312 12 28 312 13 39 340 39 02 991 12 99 330 2 91 74 25 87 657 114 64 52 CROSSWIND 65 I 079717 15 55 395 23 22 312 15 35 390 16 54 420 39 02 991 14 17 360 2 91 74 25 87 657 136 69 62 CROSSWIND 40 O 079718 12 40 315 23 23 590 12 3 312 13 39 340 39 02 991 11 02 280 3 03 77 25 87 657 125 66 57 CROSSWIND 50 O 079719 15 55 395 24 02 610 15 35 390 16 54 420 39 0...

Page 11: ...ible pipe approved for the purpose and in either case should be at least equal in size to the main pool spa circulation piping 1 Shutoff diverter valves preferably three way valves which allows for a bypass route on the inlet and outlet lines of the heater are required a to protect completely bypass the heater from any harmful chemical treatments i e Acid wash back to back super chlorinators stain...

Page 12: ...ns necessary for circuits supplying hermetic refrigeration motor compressors This heater is pre wired to work with external control systems heat on demand options and other external time clock overrides Refer to the external control system s instructions Models Power Min Circuit Ampacity Breaker Size Amp min max CROSSWIND 30 I 208 230VAC 60HZ 1PH 12A 15A 15A CROSSWIND 40 I 16A 20A 20A CROSSWIND 50...

Page 13: ... AC1 AC2 LA G DCFM MDRV OUT1A AIN8 AC N WCTIL DIN1 DIN2 DIN4 DIN5 AIN1 AIN2 AIN3 AIN4 AIN5 AIN6 AIN7 12V B A DIN3 OUT8A OUT7 OUT6 OUT1 OUT8 DCHV OUT9 T5A 250V AC L RY2 S11 S16 S15 S14 S13 S12 CN12 CN21 CN18 CN26 Electronic Expansion Valve JP1 SW1 ACIN2 ACOUT2 PB18 Pump Control YLW BRN BRN BLU YLW YLW BRN BLU BPH C N3 80 P 1 D CN1 MA1 8K16 L 2 L 1 POWER 208 230V 60Hz CL CN24 CN19 CN6 BPH011 UK 0130...

Page 14: ...DRV OUT1A AIN8 AC N WCTIL DIN1 DIN2 DIN4 DIN5 AIN1 AIN2 AIN3 AIN4 AIN5 AIN6 AIN7 DIN3 OUT8A OUT7 OUT6 OUT1 OUT8 DCHV OUT9 T5A 250V AC L RY2 S11 S16 S15 S14 S13 S12 CN12 CN21 CN18 CN26 Electronic Expansion Valve JP1 SW1 ACIN2 ACOUT2 PB18 Pump Control YLW BRN BRN BLU YLW YLW BRN BLU B P H C N 5 0 0 P 1 D Wi Fi CN1 MA2 4K16 L 2 L 1 POWER 208 230V 60Hz CL CN24 CN19 CN6 BPH012 UK G 12V B A 013094 81000...

Page 15: ...15 F10766 Crosswind 30 O 40 O 6100 64_Crosswind indd 15 11 26 2019 4 16 46 PM ...

Page 16: ...16 F10767 Crosswinds 50 O 6100 64_Crosswind indd 16 11 26 2019 4 16 46 PM ...

Page 17: ... when the HEAT PUMP is on and the screen shows Press FAN to enter Silent Mode The display screen will show NOTE Select Smart Mode for initial heating Screen Lock If no button is used within 30 seconds the screen will lock automatically At this point the backlight will turn off and 0 will display Alternatively you can lock the display by pressing the LOCK button for 3 seconds to achieve the same re...

Page 18: ... the machine is on or off 1 Press UP or DOWN to set to your required pool water temperature 2 The numbers on the LED screen will flash during adjustment 3 After five seconds of inactivity the LED will stop flashing the adjusted target temperature will be saved and the LED screen will revert to the default display 4 Later on at any time should you wish to check the temperature press UP or DOWN agai...

Page 19: ...and adjust the temperature settings for the pool or spa The temperature range is factory set from 64 F 18 C to 104 F 40 C HEAT ONLY 54 F 12 C to 86 F 30 C COOL ONLY Details on Inverter Models for starting and adjusting the settings see page 17 For On Off Models see page 18 Before Start Up Model Identification The model number of the heater can be found on the rating plate Figure 1 Water Water must...

Page 20: ...avoid damage to the heater 2 Drain water from the heater by removing the piping connection on both the inlet and outlet side from the pool to the heater As needed use a shop dry wet vac or air pressure to purge any excess water 3 Unscrew the water union of the inlet pipe top to let water flow out completely from the outlet bottom A ACAUTION If water is left in the system during freezing weather th...

Page 21: ...r anti freeze mode not a failure HEAT flashing Defrosting not a failure Table H Fault Codes On Off Models Only No Display Failure Description 1 E1 High gas pressure protection 2 E2 Low gas pressure protection 3 E3 No water flow protection 4 E4 3 phase sequence only for 3 phase heaters 5 E5 Outdoor power supply abnormality protection 6 E6 Water temp difference between in out too high insufficient w...

Page 22: ...14 600 15 000 20 295 26 970 COP 4 4 4 0 4 5 4 0 5 1 4 15 5 2 4 3 Rated input power kW 0 2 1 5 0 23 1 95 0 28 2 45 0 34 3 4 Rated input current A 0 86 6 52 1 8 48 1 22 10 65 1 48 14 78 Power supply 208 230VAC 1 Ph 60Hz Refrigerant R410A in oz 28 2 31 7 38 8 45 9 Advised water flux GPM L min 13 2 17 7 50 67 17 7 26 4 67 100 21 9 30 6 83 116 28 5 37 5 108 142 Sound pressure 39 3 m dBA 33 4 45 2 33 6 ...

Page 23: ...er circulation flow 67 100 L min 83 116 L min Noise 50 dB A 58dB A Waterproof class IPX4 IPX4 Table K Technical Parameters On Off Models Only 10 REPLACEMENT PARTS NOTE To supply you with the correct part it is important that you supply the heater model number serial number and type of gas when applicable Any part returned for replacement under standard company warranties must be properly tagged wi...

Page 24: ...000408 241812 6 fan motor H000409 H000409 H000409 H000409 241813 7 Fan blade H000410 H000410 H000410 H000410 241814 8 Electronic expansion valve coil H000411 H000411 H000411 H000411 241815 9 4 way valve coil H000412 H000412 H000412 H000419 241816 10 Water unions H000413 H000413 H000413 H000413 241817 11 Water union gasket H000414 H000414 H000414 H000414 241818 12 Full Set of Sensors H000415 H00041...

Page 25: ... H000426 H000426 H000426 241825 6 fan motor H000427 H000427 H000435 241813 7 Fan blade H000410 H000410 H000428 241814 8 Fan motor capacitor H000429 H000429 H000430 241826 9 4 way valve H000431 H000432 H000432 241816 10 Water Unions H000433 H000433 H000433 241817 11 Water union gasket H000414 H000414 H000414 241818 12 Full set of Sensors H000434 H000434 H000434 241819 13 Drain kit H000418 H000418 H...

Page 26: ...en the Applicable Warranty Periods are one 1 year parts and labor and two 2 years for parts only with no labor coverage in the second year Notwithstanding the foregoing the titanium tube component of the titanium heat exchanger is warranted for seven 7 years from the Effective Date with no labor coverage in the second through seventh years If the Heater is installed anywhere other than a single fa...

Page 27: ...r component part and to verify warranty coverage at its factory Warranty service CANNOT be initiated until the status of the warranty coverage has been established EXCLUSIVE WARRANTY LIMITATION OF LIABILITY THE LIMITED WARRANTY IS THE ONLY WARRANTY PROVIDED BY RAYPAK IN CONNECTION WITH THE HEATER AND ITS COMPONENT PARTS NO ONE IS AUTHORIZED TO MAKE ANY OTHER WARRANTIES ON RAYPAK S BEHALF ANY IMPLI...

Page 28: ...Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 1 800 260 2758 Fax 805 278 5468 Litho in U S A 6100 64_Crosswind indd 28 11 26 2019 4 16 52 PM ...

Reviews: