55M4300CCE00 Rev A
Dyno version. Must be set to OFF
for this pressure sensing version of the i4500.
ATB on Prox1 of load interface.
Optional feature, set to OFF unless load interface
module is configured to control the ATB signal. Refer to system wiring drawing
supplied.
WARNING: This setting must match the relevant wiring drawing for proper operation
of the i4300 system.
Step #8: “Picture”
This setting allows the graphic of the crane shown in the normal working window to be
set to a version that looks similar to the machine to which the system is fitted. It can be
set to any of the available choices at any time without changing the performance of the
system.
Step #9: Set the clock
The clock must be set to the correct local time and date to ensure any event recorded
by the i4300 is simple to analyze. It is not necessary to be in the calibration mode of the
i4300 for this setting, see also “System configuration mode settings” section of the
instruction manual.
1-
Press the Mode button.
2-
Scroll to highlight “Config Mode” using
“
”
or
“
”
.
3-
Press
“
”
to enter this menu, scroll down to “Date and Time” and press
“
”
again.
The date fields are displayed mm/dd/yyyy and the time fields are displayed hh:mm