DESCRIPTION
The nVent RAYCHEM TraceTek TTC-1 sensing module is used with
TraceTek sensing cables to detect liquid leaks. The module provides
visual indication when a leak or cable break has occurred and has
relay contacts to connect the TTC-1 to external devices for remote
monitoring and control.
ELECTRICAL CODES
Installation must be done in accordance with national and local
codes and regulations that apply. The TTC-1 must be installed in
ordinary areas only.
MODULE LOCATION
Enclosure rating: IP 20 / NEMA 1
Operating temperature range: 0ºC to 50ºC (32ºF to 122ºF)
SPECIFICATIONS
Maximum sensing cable length: 250 ft (76 m)
• Leader cable length is not included in the length limitation.
Input power:
• 12 to 24 Volts AC – 0.25 A
• 15 to 24 Volts DC – 0.15 A
• When using a transformer, use UL listed Class II transformer
rated at 24 V, 20 VA
Recommended fuse rating: 3 A
Relay ratings: 3 A: 30 Volts DC or 24 Volts AC
INSTALLATION MATERIALS AND TOOLS REQUIRED
Wall fastener (2 ea for surface mounting only)
PARTS AND MATERIALS
• 1 ea TTC-1 Sensing Module
• 1 ea TTC-1 Wall Label
• 4 ea Strain Reliefs
OPTIONAL ACCESSORIES
• TTC-DRC DIN Rail Clip – Part # 062825-000
• TTE-XAL External Loud Alarm – Part # 418569-000
• TT-MAP-TOOL – Part # E43135-000
APPROVALS
General Signaling Equipment
76LJ
TYPE NM
Figure 1: TTC-1 Module
4.2 in
(106 mm)
2 in
(52 mm)
4.4 in
(112 mm)
TRACETEK
IMPORTANT NOTES
• The TTC-1 module is designed for use with TraceTek sensing
cables and probes only. A TTC-1 based system will detect and
alarm on all fluid leaks detected by the TraceTek cable as per
the appropriate cable data sheet.
• Transient spills and contamination may also activate the
system. Users should consider this operational function when
determining the suitability of the TraceTek system for specific
applications.
• The system has not been designed for repetitive cycling.
• Always connect the Leak Detection relay to an annunciation
device (for example the nVent RAYCHEM TraceTek TTE-XAL
External Loud Alarm) so that an operator is notified and can
verify proper operation if automatic equipment is connected.
• Maintenance personnel should examine the sensing cable for
cleanliness and verify proper operation of the TTC-1 module at
least every six (6) months.
TTC-1
TraceTek Sensing Module Installation, Operation
and Maintenance Instructions