Rate Reads “0000”
1. Verify speed display is being registered accurately. If the speed displays
a constant zero value, troubleshoot the speed sensor.
2. Verify that the console is registering flow by confirming the total volume
display is correct.
3. If the total volume display is incorrect, seethe “Rate does not change in
either manual or automatic control modes” for resolution.
Rate display is inaccurate or
unstable.
1. Verify that all calibration values are entered correctly on the console (see
the console operation manual for instructions).
2. Verify the speed display is registering accurately.
If speed display is inaccurate, troubleshoot the speed sensor.
3. In manual (MAN) control mode, verify that the rate display holds a
constant value.
4. Hoses connecting the AccuFlow system should not exceed 15’ [4.5 m] of
1-1/2” hoses and a 1-1/2” breakaway.
5. Remove any street elbows and replace with a conventional elbow and
nipple.
6. Refer to the Chapter 7,
, to clean the flow meter and y-
strainer screen and magnet assemblies. These procedures should be
performed periodically or when system performance degrades. Be sure
to follow the instructions in the
Discharging the AccuFlow™ System
section on page 61 before performing maintenance on the AccuFlow
system.
7. Verify that the nurse tank has a high flow valve.
Rate does not change in either
manual or automatic control
modes.
1. Check the control valve cabling for wear and breaks.
2. Check and clean cable connections as necessary.
3. Check the voltage at the control valve connector by:
a. Powering on the console.
b. Set the master switch to the ‘on’ position.
c. Set all products or the console to manual (MAN) control mode.
NOTE:
For multi-section systems, disconnect section 1 on/off valve.
Turn section 1 on and all other sections off. This avoids opening
section valves and accidental release of NH
3
.
4. Hold the increase/decrease (INC/DEC) switch. With the INC/DEC switch
in operation, check for movement & voltage at the control valve.
5. Verify that valve is turning by watching the coupler shaft. If the valve
does not open or close, replace the control valve motor.
Total volume does not register
1. Test the flow meter cable and any extension cables for breaks or shorts.
Refer to the console operation manual for testing procedure.
2. Check and clean internal components of flow meter. Refer to the console
operation manual for flow meter cleaning and adjustment procedure.
Total volume registers flow
inaccurately.
1. Verify product flow corresponds to the direction of the arrow stamped
on the flow meter.
2. Clean flow meter according to the
3. See console installation manual.
Issue
Resolution
Summary of Contents for AccuFlow HP+
Page 20: ...CHAPTER 2 16 AccuFlow Vortex and AccuFlow HP Installation and Operation Manual ...
Page 46: ...CHAPTER 3 42 AccuFlow Vortex and AccuFlow HP Installation and Operation Manual ...
Page 54: ...CHAPTER 4 50 AccuFlow Vortex and AccuFlow HP Installation and Operation Manual ...
Page 64: ...CHAPTER 5 60 AccuFlow Vortex and AccuFlow HP Installation and Operation Manual ...
Page 74: ...CHAPTER 6 70 AccuFlow Vortex and AccuFlow HP Installation and Operation Manual ...
Page 94: ...CHAPTER 8 90 AccuFlow Vortex and AccuFlow HP Installation and Operation Manual ...