12

Installation of the unit into the Housing 

Installations of the unit into the wall 

1. Slide the unit into the housing until it is firmly against the
    rear of the housing. Care is required to ensure the foam
    sealing strips on the housing remain in position. 
2. Connect the air conditioner to the power and position
    excess cord length beneath the air conditioner base.
3. Engage the chassis fixing brackets into the bottom housing
    rail and secure to the base with the screw provided.
4. Remove the front panel from it's carton and plastic bag
    and fit as per the Installation lnstruction.
5. Switch unit on. Check for operation of the unit and check
    for vibration in the installation.
6. Fit the drain pan to the housing and run a drain line to a 
    suitable location if required.

Alternative method of installation if external 
support cannot be provided.

FLASH OR SEAL AROUND EXTERNAL 
WALL FRAME OR ARCHITRAVE

STURDY TIMBER
FRAME

TIMBER FRAMED 
WALL OR PARTITION

SOLID TIMBER SUPPORT

STEADYING BRACKET
(ONE PER SIDE)

DRAIN PAN

ENSURE LOUVRES
ARE ENTIRELY 
OUTSIDE THE WALL

AIR IN

AIR IN

AIR OUT

100mm minimum

OPTION A

AIR IN

LOUVRE

BRICK
WALL

O

45  BRICK CUT AWAY 
TO CLEAR LOUVRES

FRONT

AIR OUT

AIR IN

AIR IN

TOP

VIEW

O

45  BRICK CUT AWAY 
TO CLEAR LOUVRES

100mm

BRICK
WALL

100mm

OPTION B

Step 1

Remove the air conditioner from it's packaging, remove fixing
screws and slide the air conditioner out of it's housing (Refer
to Installation Steps).

Step 2

Prepare the hole in the wall so that the bottom of the housing 
is well supported, the top has minimum clearance and the air 
inlet louvers have clearance as shown below in options  A and
B. Holes from the outside through to the cavity should be 
sealed. The housing should slope down towards the rear by 
about 5mm to allow water formed during operation to drain.

Step 3

Install the housing into the wall and secure. Ensure the foam
seals are not damaged. Flash, seal or fill gaps around the 
inside and outside to provide satisfactory appearance and 
protection against the weather, insects and rodents.
 

Installation of the Housing 

NOTE: UNIT MAY BE SUPPORTED BY A 
            SOLID FRAME FROM BELOW OR 
            BY A HANGER FROM A SOLID
            OVERHEAD SUPPORT.

Preferred method of installation into a timber 
framed wall, partition or window.

FLASH OR SEAL AROUND EXTERNAL 
WALL FRAME OR ARCHITRAVE

STURDY TIMBER
FRAME ALL ROUND 
UNIT

TIMBER FRAMED 
WALL OR PARTITION

EXTERNAL SUPPORT 
FRAME AT BALANCE
POINT OF A/C

ALTERNATIVELY, BRACKETS 
AS ILLUSTRATED BELOW
MAY BE USED.

DRAIN PAN

Summary of Contents for RC-X7T

Page 1: ...TYPE R O O M A IR CO N D ITIO N ER R 410A W IN D O W W A LL TYPE R O O M A IR CO N D ITIO N ER R 410A W IN D O W W A LL TYPE R O O M A IR CO N D ITIO N ER R 410A W IN D O W W A LL TYPE R O O M A IR CO N D ITIO N ER R 410A W IN D O W W A LL TYPE R O O M A IR CO N D ITIO N ER R 410A W IN D O W W A LL TYPE R O O M A IR CO N D ITIO N ER R 410A W IN D O W W A LL TYPE R O O M A IR CO N D ITIO N ER R 410...

Page 2: ...xperience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play the appliance Cleaning and user maintenance shall not be made by children without supervision EN Standard requirements This appliance is not intended for use by persons including children with reduced physical sensory o...

Page 3: ...ool the entire house It may cause explosion fire and burns It may cause electric shock or fire due to heat generation It may cause electric shock It may cause failure of machine or electric shock It may cause fire and electric shock It may cause fire and electric shock It may cause electric shock or fire If the power cord is damaged it must be replaced by the manufac turer or an authorised service...

Page 4: ...es food pets plants and art objects It may cause deterioration of quality etc It may cause failure of product or fire Do not use for special purposes Turn off the main power switch when not using the unit for a long time If water enters the unit turn the unit off at the power outlet and switch off the circuit breaker Isolate supply by taking the power plug out and contact a qualified service techn...

Page 5: ...njuries can occur when handling sharp metal edges 2 Do not use water to clean inside the air conditioner Exposure to water can destroy the insulation leading to possible electric shock 3 When cleaning the unit first make sure that the power and circuit breaker are turned off Note Performance may be reduced outside of these operating temperatures 1 Power cord conductors are distinguished according ...

Page 6: ...tions are the same The following illustration is for explanation purpose only the actual shape of the machine you purchased may be slightly different NOTE All the illustrations in the manual are for explanation purpose only Your air conditionar may be slightly different The actual shape shall prevail 9 10 TEMP AUTO COOL DRY FAN HIGH MED LOW MODE FAN SPEED SWING TIMER ON ECONOMY ON OFF TIMER OFF RE...

Page 7: ...ion OPEN the vent to discharge stale air The electronic control keypad will look like one of the following CLOSE VENT OPEN To open the vent pull the lever toward you To close it push it in To open the vent set the lever to the right position To close it set the lever in the left position CLOSE OPEN NOTE The outline of the operation panel is based on typical model the function is the same with your...

Page 8: ...ed setting Each depression of the keypad will alternate through LOW MED some models without HIGH fan speed options The green indicator light beside the FAN speed option will illuminate identifying the fan speed selected Press the TIMER keypad to activate the auto start auto stop timer function Auto start stop programs can be set from 0 24 hours Each depression of the TIMER keypad will increase or ...

Page 9: ...n mode When the actual room temperature is 2 C below the set point the unit will operate in Heat mode Note If activating the SLEEP mode when the unit is operating on AUTO mode the fan motor will changed into LOW speed mode immediately ECONOMY SLEEP For the models with SWING feaure press and hold the ECONOMY keypad for 2 seconds or use the remote control to activate the ECONOMY feature Press and ho...

Page 10: ...nt failure The air filter behind the inlet grille should be checked and cleaned at least once every 2 weeks or as necessary to maintain optimal performance of the air conditioner How to remove the air filter 1 Hold the tabs under the front panel then uplift it outwards and remove the front panel 2 Pinch the handle under the air filter and make the air filter arched remove it from the slot from und...

Page 11: ...cabinet and attach to the back drain hole For the units without the bottom rubber plug just install the drain tray 2 Take out the drain tray and screws which provided with your air conditioner accessory 3 Install the drain tray at the bottom of the unit and secure with screws provided 4 Connect the drain hose to the outlet located at one side of the drain tray You can purchase the drain hose or tu...

Page 12: ...ir will greatly reduce the cooling and heating efficiency of the air conditioner 4 Install the unit a little obliquely outward not to leak the condensed water into the room about 10mm or 1 4 bubble with level 5 Install the unit with its bottom portion 75 150cm above the floor level 6 The power cord must be connected to an independent circuit The yellow green wire must be grounded Over 50cm About 1...

Page 13: ...RICK CUT AWAY TO CLEAR LOUVRES FRONT AIR OUT AIR IN AIR IN TOP VIEW O 45 BRICK CUT AWAY TO CLEAR LOUVRES 100mm BRICK WALL 100mm OPTION B Step 1 Remove the air conditioner from it s packaging remove fixing screws and slide the air conditioner out of it s housing Refer to Installation Steps Step 2 Prepare the hole in the wall so that the bottom of the housing is well supported the top has minimum cl...

Page 14: ...binet See Fig 8 5 Install the two chassis fixing brackets using the two fixing screws See Fig 5 Step 4 Install the frame 1 Install the frame and connect the coupler plugs making sure not to interfere with the temperature sensor cable See Fig 9 2 Fix the screws on the frame See Fig 3 Step 5 Install the air filter and front panel 1 Install the air filter into the frame s slot from upside to undersid...

Page 15: ...compressor has cycled off The fuse is blown circuit breaker is tripped Check the house fuse circuit breaker box and replace the fuse or reset the breaker Power failure If power failure occurs switch off and disconnect unplug the power cord When power is restored reconnect plug in the power cord switch on the power and wait 3 minutes to restart the air conditioner to prevent tripping of the compres...

Page 16: ...15 SPECIFICATIONS Model Unit Dimension mm W x H x D Wirning Size m m 2 450x346x585 3 1 5 RC X7T Cooling Capacity Btu h 7000 RC X9T 9000 450x346x585 3 1 5 ...

Page 17: ...驗的人來使用 孩童不得 胡亂使用本裝置 本裝置的清潔與維護也不得由孩童在無人監督下進行 EN標準 除非有適當人員監督下或給予如何安全使用本機的指示並讓其了解涉及的風險 本機並非設計給 運動 感官與感知能力受限 或缺乏相關知識或使用經驗的人 包括孩童 來使用的 IEC標準 本機旁有孩童時應有成人監督 確保他們不會胡亂使用本裝置 若電源線受損時 必須由製造商 其維護代理商或合資格的技術人員來更換 以免發生危險 本裝置的安裝應根據國家電線安裝的相關法例進行 有電氣加熱器的家電必須與易燃物件相隔至少一公尺的距離 本機需要修理或維護時須聯絡合資格的技術人員 ...

Page 18: ... ...

Page 19: ...3 ...

Page 20: ...O 18 43 C T1 O 17 32 C T1 O 5 24 C T1 O 0 27 C T1 注 ...

Page 21: ...5 Õ µ ú Á ã þ Ã û Æ 附件 1 1 螺絲 排水接頭 1 排水接盤 2 注 本說明書中的所有插圖僅供說明用途 您的空調可能略有不同 以實際形狀為準 密封圈 用於排水接頭 數量 ...

Page 22: ......

Page 23: ...某些型號沒有中風速 自動 模式 風速固定為 高 ...

Page 24: ...8 只限冷暖型號 注意 如果在本機處於AUTO模式時激活SLEEP模式 風扇馬達將立即變為LOW速度模式 自動 AUTO ...

Page 25: ...開 空氣過濾網 進氣格柵後面的空氣過濾網應至少每2週 或根據需要 進行一次檢查和清潔 以保持空調的最佳性能 如何拆卸空氣過濾網 1 抓住前面板下方的卡舌 然後向外抬起 然後卸下前面板 2 捏住空氣過濾器下方的手柄 使空氣過濾器成拱形 將其 從下側向上移出 3 用溫肥皂水清潔過濾網 水應低於40 以防止過濾網變形 4 沖洗乾淨 輕輕抖掉過濾網中的多餘水分 安裝前請讓 過濾網充分乾燥 為防止過濾網變形 請勿在陽光直射下 晾乾 注 當出現上述其中一類故障時 請關掉空調機 檢查有誤堵塞 重啟空調機 如果故 障依舊 請再次關掉空調機并拔下電源線 聯繫信興電器服務中心有限公司熱線查詢 2406 5666 ...

Page 26: ...1 將密封件安裝到排水接頭上 與空調附件一起提供 2 從設備背面取下橡膠塞 如果適用 然後將橡膠塞 隨空調附件提供 插入設備的底部排水孔 3 將排水接頭連接到機櫃後部 在此處卸下插頭並旋轉 90 以牢固地組裝 4 連接排水接頭和延長排水管 請自己購買 注意 如果您選擇不排水 則裝置的底部和後部排水孔應插入橡膠塞 建議 為確保冷凝水順利排出 安裝排水盤時 請務必將排水盤的排水口向下放置 ...

Page 27: ...11 ...

Page 28: ......

Page 29: ......

Page 30: ...異常操作 ...

Page 31: ...品若有技術改進 會編進新版說明書中 恕不另行通知 產品外觀及規格 以廠方生產資料為準 售後服務 由購買日期起之一年保修期內 經信興電器服務中心有限公司之服務人員證實產 品故障屬於正常使用之情況下發生者 本公司將提供免費維修或更換零件服務 經更換之任何損壞零件 將歸屬本公司所有 用戶請於維修時出示購買收據 換 購收據及蓋有銷售點 換購中心印章的保修證 如有任何疑問 請致電信興電器 服務中心有限公司熱線查詢 2406 5666 冷卻效能 Btu h 型號 7000 機身尺寸 mm 3 1 5 450x346x585 RC X9T 9000 寬x高x深 配線規格 ...

Page 32: ...RIES HONG KONG 電話 Tel 852 2406 5439 傳真 Fax 852 2408 1389 澳門慕拉士大馬路193 199號南嶺工業大廈5樓I座 AVENIDA DE VENCESLAU DE MORAIS NO 193 199 5 ANDAR I EDF INDUSTRIAL NAM LENG MACAU 電話 Tel 853 2836 2928 傳真 Fax 853 28336405 有關最新之客戶服務中心資訊 請參閱信興服務中心網址 www shesc com 或致電維修服務熱線查詢 For the latest information of customer service centres please visit www shesc com or call us at our hotline 信興電工工程有限公司 SHUN HING ELECTRIC WOR...

Reviews: