Appendix J: Integration
799
Connecting a Rack PDU
To connect the Raritan PX to the KSX II:
1.
Connect one end of a Cat5 cable to the following ports of different
Raritan PX.
PX1 series: RJ-45 "SERIAL" port
PX2, PX3 or PX3TS series: RJ-45 "FEATURE" port
2.
Connect the other end of the Cat5 cable to either the Power Ctrl. 1 or
Power Ctrl. 2 ports on the back of the KSX II.
3.
Attach an AC power cord to the target server and an available rack
PDU outlet.
4.
Connect the rack PDU to an AC power source.
5.
Power on the KSX II device.
Important: When using CC-SG, the power ports should be inactive
before attaching rack PDUs that were swapped between the power
ports. If this is not done, there is a possibility that the number of
power outlets will not be correctly detected, especially after
swapping 8 and 20 outlet rack PDU models.
Diagram key
KSX II
PX SERIAL or
FEATURE port
KSX II Power
Ctrl. 1 Port or
Power Ctrl. 2
Port
Cat5 cable
PX