Chapter 6: Using the Web Interface
173
Power Transfer Settings
The following are the factory-default transfer settings:
The front panel Manual Transfer button is enabled.
Automatic retransfer is enabled.
Wait time prior to performing automatic retransfer is set to 15
seconds.
Perform automatic retransfer only when inlets are in phase.
These default behaviors can be changed by modifying the following
fields.
Field
Description
Name
Customize the PX3TS device name.
Allow Front Panel
Transfer
Enable/disable the front panel Manual
Transfer button.
If the Manual Transfer button is disabled,
the Manual Disabled indicator lamp on the
front panel is lit.
Automatic Retransfer
Three options are available.
Never: Disable automatic retransfer.
Always: Enable automatic retransfer and
inlet phase synchronization is NOT
required.
Only if phases are in sync: Automatic
retransfer is performed only when inlets
are in sync.
See
Automatic Retransfer
(on page 82).
Retransfer Wait Time
Enter the time (seconds) preferred inlet
power must be in the normal state before
retransfer occurs.
Summary of Contents for PX3TS
Page 5: ......
Page 16: ...Contents xvii Index 807...
Page 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Page 85: ...Chapter 4 Connecting External Equipment Optional 61...
Page 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Page 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Page 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Page 792: ...Appendix I Additional PX3TS Information 768...