Chapter 8: Using the Command Line Interface
489
Setting the Outlet Initialization Delay
This section applies to outlet-switching capable models only.
This command determines the outlet initialization delay timing on device
startup. See
PDU
(on page 157) for information on outlet initialization
delay.
config:#
pdu outletInitializationDelayOnDeviceStartup <timing>
Variables:
<timing> is a delay time between 1 and 3600 seconds.
Note: This feature does NOT take effect and cannot be configured on a
PX3 device after the outlet relay is set to the "Latching" mode. See
PX3
Latching Relay Behavior
(on page 162).
Specifying Non-Critical Outlets
This section applies to outlet-switching capable models only.
This command determines critical and non-critical outlets. It is
associated with the load shedding mode. See
Load Shedding Mode
(on
page 181).
config:#
pdu nonCriticalOutlets <outlets1>:false;<outlets2>:true
Separate outlet numbers and their settings with a colon. Separate each
"false" and "true" setting with a semicolon.
Variables:
<outlets1> is one or multiple outlet numbers to be set as critical
outlets. Use commas to separate outlet numbers.
Use a dash for a range of consecutive outlets. For example,
3-8
represents outlets 3 to 8.
<outlets2> is one or multiple outlet numbers to be set as
NON-critical outlets. Use commas to separate outlet numbers.
Use a dash for a range of consecutive outlets. For example,
3-8
represents outlets 3 to 8.
Summary of Contents for PX3-3000 series
Page 5: ......
Page 18: ...Contents xviii Index 841...
Page 93: ...Chapter 4 Connecting External Equipment Optional 69...
Page 787: ...Appendix J RADIUS Configuration Illustration 763 Note If your PX3 uses PAP then select PAP...
Page 792: ...Appendix J RADIUS Configuration Illustration 768 14 The new attribute is added Click OK...
Page 793: ...Appendix J RADIUS Configuration Illustration 769 15 Click Next to continue...
Page 823: ...Appendix K Additional PX3 Information 799...