Appendix F: PX3 Models with Residual Current Monitoring
594
3.
Set up RCM thresholds.
a.
Enable or disable the RCM critical threshold. Residual current
greater than this value triggers Critical RCM state.
b.
Enable or disable the RCM warning threshold. Residual current
greater than this value triggers Warning RCM state.
c.
Determine the residual current decrease to end Warning or
Critical RCM state.
d.
Click Save.
4.
Click 'Start Self Test' to run RCM self-test.
Scheduling RCM Self-Test
You can have the PX3 run RCM self-test automatically at a regular time
interval or on a specific date and time. See
Scheduling an Action
(on
page 306) for the procedure and select "Start residual current monitor
self test" to create the scheduled RCM self-test action.
Disabling or Enabling Front Panel RCM Self-Test
You can enable or disable the function of performing the RCM self-test
by operating the front panel buttons. By default, this function is enabled.
To disable or enable the front panel RCM self-test:
1.
Choose Device Settings > Front Panel.
2.
Do either below:
To disable this function, deselect the "Perform RCM self-test"
checkbox.
To enable this function, select the "Perform RCM self-test"
checkbox.
3.
Click Save.
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...