Chapter 4: Connecting External Equipment (Optional)
40
Supported Maximum DPX Sensor Distances
When connecting the following DPX sensor packages to the PX, you
must follow two restrictions.
DPX-CC2-TR
DPX-T1
DPX-T3H1
DPX-AF1
DPX-T1DP1
Sensor Connection Restrictions:
Connect a DPX sensor package to the PX using the sensor cable
pre-installed (or provided) by Raritan. You MUST NOT extend or
modify the sensor cable's length by using any tool other than the
Raritan's sensor hubs.
If using a DPX-ENVHUB4 sensor hub, the cabling distance between
the PX and the sensor hub is up to 33' (10 m).
Maximum Distance Illustration:
The following illustrates the maximum distance when connecting DPX
sensor packages with a maximum 16' (5 m) sensor cable to a PX via a
sensor hub.
The sum of a DPX-T3H1 sensor cable's length is 16' (5 m).
The total cabling length between the PX and one DPX-T3H1 is 49'
(15 m) as illustrated below.
Note that the length 16' (5 m) is the length of each DPX-T3H1 sensor
cable, which is defined in the above diagram.
PX
33' (10 m)
cable
1 sensor hub
16' (5 m)
cable
Up to 4 DPX-T3H1
sensor packages
Summary of Contents for PX2-1000 SERIES
Page 5: ......
Page 71: ...Chapter 4 Connecting External Equipment Optional 52...
Page 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Page 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Page 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Page 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...