Chapter 8: Using the Command Line Interface
347
Overcurrent Protector Information
This command is only available for models with overcurrent protectors
for protecting outlets.
This command syntax shows the overcurrent protector information, such
as a circuit breaker or a fuse.
#
show ocp <n>
To show detailed information, add the parameter "details" to the end of
the command.
#
show ocp <n>
details
Variables:
<n> is one of the options:
all
, or a number.
Option
Description
all
Displays the information for all overcurrent
protectors.
Tip: You can also type the command without
adding this option "all" to get the same data.
A specific
overcurrent
protector
number
Displays the information for the specified
overcurrent protector only.
Displayed information:
Without the parameter "details," only the overcurrent protector status
and name are displayed.
With the parameter "details," more overcurrent protector information
is displayed in addition to status, such as the rating and RMS current
value.