background image

General 

Description

The  Tyco

®

  Rapid  Response

™ 

Series 

LFII  (TY3596)  Residential  Concealed 

Pendent Sprinklers are decorative, fast 

response, fusible solder sprinklers de-

signed for use in residential occupan-

cies such as homes, apartments, dor-

mitories, and hotels.
The cover plate assembly conceals the 

sprinkler operating components above 

the ceiling. The flat profile of the cover 

plate  provides  the  optimum  aestheti-

cally  appealing  sprinkler  design.  In 

addition,  the  concealed  design  of  the 

Series LFII (TY3596) provides 1/4 inch 

(6,4 mm) vertical adjustment. This ad-

justment  provides  a  measure  of  flexi-

bility with regard to which the length of 

fixed pipe drops to the sprinklers must 

be cut. 
The  Series  LFII  are  to  be  used  in  wet 

pipe  residential  sprinkler  systems  for 

one-and two-family dwellings and mo-

bile  homes  per  NFPA  13D;  wet  pipe 

residential  sprinkler  systems  for  resi-

dential occupancies up to and includ-

ing  four  stories  in  height  per  NFPA 

13R; or, wet pipe sprinkler systems for 

the  residential  portions  of  any  occu-

pancy per NFPA 13. 
The  Series  LFII  (TY3596)  has  a  4.9 

(60,5)  K-factor  that  provides  the  re-

quired residential flow rates at reduced 

pressures, enabling smaller pipe sizes 

and water supply requirements. 
The Series LFII (TY3596) has been de-

signed with heat sensitivity and water 

distribution  characteristics  proven  to 

help  in  the  control  of  residential  fires 

and  to  improve  the  chance  for  occu-

pants to escape or be evacuated. 
The  Series  LFII  (TY3596)  Residen-

tial Concealed Pendent Sprinklers are 

shipped  with  a  Disposable  Protective 

Cap.  The  Protective  Cap  is  temporar-

ily  removed  for  installation,  and  then 

it can be replaced to help protect the 

sprinkler  while  the  ceiling  is  being  in-

stalled or finished. The tip of the Pro-

tective Cap can also be used to mark 

the center of the ceiling hole into plas-

ter  board,  ceiling  tiles,  etc.  by  gently 

pushing  the  ceiling  product  against 

the  Protective  Cap.  When  the  ceiling 

installation  is  complete  the  Protective 

Cap  is  removed  and  the  Cover  Plate 

Assembly installed. 

notice

The  Series  LFII  (TY3596)  Residential 

Concealed  Pendent  Sprinklers  de-

scribed  herein  must  be  installed  and 

maintained  in  compliance  with  this 

document  and  with  the  applicable 

standards  of  the  National  Fire  Pro-

tection  Association,  in  addition  to  the 

standards of any authorities having ju-

risdiction. Failure to do so may impair 

the performance of these devices. 
The owner is responsible for maintain-

ing their fire protection system and de-

vices  in  proper  operating  condition. 

The  installing  contractor  or  sprinkler 

manufacturer  should  be  contacted 

with any questions. 

Sprinkler/Model 

Identification 

Number

SIN TY3596

Series LFII Residential 

Concealed Pendent Sprinklers, Flat Plate  

4.9 K-factor

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Page  of 6  

MAY, 2008 

TFP442

iMPoRtAnt

Always  refer  to  Technical  Data 

Sheet  TFP700  for  the  “INSTALLER 

WARNING”  that  provides  cautions  

with  respect  to  handling  and  instal-

lation of sprinkler systems and com-

ponents.  Improper  handling  and  in-

stallation  can  permanently  damage 

a sprinkler system or its components 

and  cause  the  sprinkler  to  fail  to  

operate in a fire situation or cause it  

to operate prematurely.