Issue 1 – September 2003

  

 

Page 

RAIPC

    Rako Intelligent Partition Control Module – Installation and Operating Instructions. 

 

General 

 

The Rako RAIPC is an intelligent partition control unit designed for use 
rooms that are divisible into smaller rooms by demountable partitions. 

The unit accepts inputs from up to 2 partitions giving a total of 3 
individual rooms or combinations thereof.  (see fig 1). With local control 

panels located in each of the rooms and with both partitions closed, each 
of the control panels will control their respective rooms. Opening the 

partition between rooms 1 and 2 will allow the scenes in both rooms to be 
selected from either of the control panels. This follows for the other room 

combinations as shown in fig 1 below.   

Initial configuration is achieved using the RASOFT programming software.   
 

 

Room 5

Room 6

Room 7

Partition 1

(Closed)

Partition 2

(Closed)

(Selects scenes

 in room 5 only)

(Selects scenes

 in room 6 only)

(Selects scenes

 in room 7 only)

Partition Combination 1

Room 5

Room 6

Room 7

Partition 1

(Open)

Partition 2

(Closed)

(Selects scenes

 in rooms 5 and 6)

(Selects scenes

 in room 7 only)

Partition Combination 2

(Selects scenes

 in rooms 5 and 6)

Room 5

Room 6

Room 7

Partition 1

(Closed)

Partition 2

(Open)

(Selects scenes

 in room 5 only)

Partition Combination 3

(Selects scenes

 in rooms 6 and 7)

(Selects scenes

 in rooms 6 and 7)

Room 5

Room 6

Room 7

Partition 1

(Open)

Partition 2

(Open)

Partition Combination 4

(Selects scenes

 in rooms 6, 7 and 8)

(Selects scenes

 in rooms 6, 7 and 8)

(Selects scenes

 in rooms 6, 7 and 8)

 

 

Fig 1 – Room Combinations 

 

 
 

 

 

 

 

 

 
 

  

Fig 2. 

Front View of Components 

 

 

Installation 

 

Before commencing installation of the Rako RAIPC interface module first 
read this instruction manual carefully. 

Rako Controls Ltd accepts no responsibility for any damage or injury 
caused by incorrect installation of a Rako product. 

 
 

The RAIPC is designed for applications where a room is to be divisible 

into smaller rooms as shown opposite. The unit has 2 volt free switched 
inputs indicating the status of the partitions. Depending on the 

installation and customer preference, the switch inputs can come from a 
variety of devices from manually operated key-switches to proximity 

switches located on the partitions.  
The RAIPC unit requires the use of the RAPSU external power supply. Or 

other 12V d.c. power supplies conforming to SELV requirements.  
Connect the power supply and the volt free switch inputs as shown in Fig. 

3 below. 

The RAIPC is supplied complete with 2 external aerials. For best 
performance these should be fixed at an angle of 90

0

 or greater to each 

other. 
 

RAPSU

power 
Supply unit

+12V DC

0V

Transmit Aerial

To be mounted at 90° to the direction of the receivers

Tx

Rx

Gnd

0v

+12v

Common

SW 2

SW 1

SWITCH 1

SWITCH 2

Receive Aerial

To be mounted at 90° to the direction of the receivers

 

 

Fig 3. 

Connection Detail

 

 

Interface 

Housing 

Protective 

Insert

Ext aerial & 

PSU Terminals 

Terminal 
Cover 

Fixing Screws 