D9210B Operation & Installation Manual
© 1997 Radionics
Page 5
Introduction
The D9210B Access Control Interface
1
PWR +
7
SDIB
6
SDIA
5
COM
8
T +
10
ZN +
9
ZNCOM
2
LCKN/C
3
LCKCOM
4
LCKN/O
13
REX
12
COM
11
RTE
16
DATA 1
17
BUZZER
18
LED
15
DATA 0
14
+5.20V
D0
READER
OPER
MON
D1
READER
1
2
3
4
5
6
ON
D9210B
Terminal
Blocks
Diagnostic and
Status LEDs
EPROM
DIP Switch
Relay
Figure 1. D9210B Access Control Interface Module
Terminal Blocks. The D9210B comes with three banks of terminal blocks for
connecting the D9210B to its power source, the panel and associated readers
and relays.
Relay. A removable (model D136) relay provides a dry contact single pull, double
throw output.
Dipswitch. The D9210B dipswitch has six on-off switch settings. Setting these
switches allows each unique D9210B to be programmed for a specific address.
EPROM. The D9210B is controlled by a programmable read-only memory
microprocessor.
Diagnostic and Status LEDs. The D9210B has a series of light emitting diodes
(LEDs) for identifying operational and diagnostic states. These are listed below.
LED
Action
State
Operational Monitor (Green)
LED blinks on and off
System is operational
LED is on or off (solid)
System is off or not operational
D0 Reader (Green)
LED rapidly blinking
Card data executing
LED is off
No card data is being received
D1 Reader (Yellow)
LED rapidly blinking
Card data executing
LED is off
No card data is being sent
Table 1. D9210B Diagnostic and Status LEDs