32206C 3/97
D9210B Operation & Installation Manual
© 1997 Radionics
Page 10
Step 3: Mounting
CAUTION
Do not install or replace a D9210B while it is connected to live power
circuits. The D9210B should be powered down until it is ready to be tested.
D9210BLC
1. Mount the D8103, D8109 or D8108A enclosure on a flat service.
2. Install another D9210LC to the mounting skirt (optional) prior to step 3.
3. Hang the mounting skirt in the enclosure by aligning the rectangular tabs of
the enclosure with the rectangular knockouts on the mounting skirt.
4. Insert the #6x3/8” screw on the bottom tab of the mounting skirt and tighten
1/4 turn to seat it. This completes the mounting of the skirt in the enclosure.
D9210B
1. Remove the cover of the D9210B by loosening the two cover screws.
2. Remove the required knockouts prior to replacing the cover.
3. Mark the holes provided for mounting the bottom half of the unit to a wall or
ceiling.
4. Screw the provided screws in to the marked service and allow a 1/4” gap
between the surface and bottom of the screw.
5. Hang the unit and secure the screws. Replace the cover and cover screws.
D9210BLC
1. The unit can be installed in a D8103, D8109 or D8108A enclosure by
matching the three plastic mounting anchors to the three hole foot prints
provided around the sides of the enclosure (4).
2. The unit can be added to a D9210BC by matching the three plastic mount
anchors to the available three hole foot prints below the factory installed
D9210B.
3. To secure the unit, use the three #8-3/4” screws provided.
Step 4: Door Contact (Onboard) Point, Terminals 9 and 10
Description. The D9210B monitors the sensor loop between the input terminal
10 and the common terminal 9 for normal, shorted, or open conditions. This loop
is provided for a door contact. The door contact can be programmed as a
perimeter, interior, or 24 hour burglar alarm point.
See the D9210B Program Entry Guide (32207) for assigning a point to the door
controller and the panel Program Entry Guide for the point types.
Point Sensor Loop. Install a 1k
Ω
resistor at the door contact, not at the
terminal of the input. This will provide supervision against grounds on the loop.
You can connect only one contact, that being the door, to this input.