background image

D2012 Installation Manual

Page 11

© 1997 Radionics

8/11/97   P/N 35122B

Check for Alarm Verification

You must check the Alarm Verification box in the
lower left hand corner of the Label if you programmed
Point 1 for Fire with Verification (Digit 1 = 2). 
See
POINT CODES in the Program Entry Guide for more
information.

Test the System

After finishing installation and programming, make a
complete functional test of the system. Test the panel and
all devices for proper operation. Test after you first
program the panel and after any subsequent programming
session.

Clear after test:  To clear the alarm memory and report
buffer, close the Standby Switch for 2 seconds, then re-
lease it. The panel returns to service in the disarmed state.

Detailed Description

Primary (AC) Power Circuit

A 16.5 VAC, 25VA transformer (Radionics model D1625) is
the primary power source for the panel.

The AC power circuit provides 1.0 Amps of rectified DC
power. The panel reserves 140mA of this power for
internal operations and 500mA for continuously powered
devices. Under alarm conditions 860mA of power is
available for continuously powered and alarm indicating
devices combined.

Transient suppressors and spark gaps protect the circuit
from power surges. This protection relies on the ground
connection. Make sure the panel’s ground terminal is
connected to a proper ground.

AC Power Failure
The panel indicates an AC power failure when power at
the terminals labeled 16.5VAC is missing for 60 seconds.
The 

AC Fail Buzz/Rpt program item sets the panel’s

response to detected AC failure. The panel indicates an
AC power restoral 60 seconds after power restores to the
terminals labeled 16.5VAC.

Secondary (DC) Power

A 12V, 4.0 Ah sealed lead-acid rechargeable battery
(Radionics D1240) supplies secondary power for auxiliary
and alarm outputs. The battery also powers the system
during interruptions in primary (AC) power.

Lead Acid Batteries Only:  The panel charging circuit is
only calibrated for lead-acid batteries. Do not use gel-cell
or nicad batteries.

Larger Battery Increases Backup Time:  To increase
battery backup time, connect a larger capacity battery, up
to 7 Ah (Radionics D126).

Battery Replacement
Radionics recommends battery replacement every three
to five years under normal use. Exceeding the maximum
output ratings, or installing the transformer in an outlet
that is routinely switched off, causes heavy discharges.
Routine heavy discharges can lead to premature battery
failure.

D135A Prevents Deep Discharge:  The D135A Low
Battery Cutoff Module protects the battery from deep
discharge during extended power outages. Deep dis-
charge can cause permanent battery damage.

Battery Supervision
When the battery drops to 12.1 VDC the keypad indicates
a trouble condition. The panel transmits a 

BATTERY LOW

report.

When the battery voltage returns to 13.0 VDC and there is
AC power at the terminals labeled 16.5VAC, the keypad
returns to normal operation. The panel transmits a

BATTERY RESTORAL 

report.

Investigate low battery reports right away:  If primary
(AC) power is off and the discharge continues, the panel
becomes inoperative when the battery voltage drops
below 10.2 VDC.

If the battery is disconnected, it takes 60 seconds for
the panel to recognize the condition.

Figure 9:  Programmer Jack

www.PDF-Zoo.com

firealarmresources.com

Summary of Contents for D2012

Page 1: ...8 11 97 P N 35122B 1997 Radionics D2012 Control Communicator Installation Manual www PDF Zoo com firealarmresources com ...

Page 2: ...so you will be advised of your right to file a complaint with the FCC if you believe it is necessary The telephone company may make changes in its facilities equipment operations or procedures that could affect the operation of the D2012 If this happens the telephone company will provide advance notice in order for you to make the necessary modifications to maintain uninterrupted service If you ex...

Page 3: ...uxiliary Power 8 Checking Continuous Current Draw 8 External Relays 8 Connect the Points 8 Point 1 8 Points 2 to 6 9 Point Wiring Diagram 9 Make the Telephone Connections 10 Power Up 10 Program the Panel 10 Unlock the Standby Switch 10 Fill out the Delay Chart 11 Test the System 11 Detailed Description 11 Primary AC Power Circuit 11 Secondary DC Power 11 Power Outputs 12 Telephone 12 Points 13 Key...

Page 4: ...5 Keypad Installation Sheet 31945 Security System User s Guide 71 07117 000 Getting Started with Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 D206 Keypad Each D206 includes the following D206 Keypad Installation Sheet 31946 Security System User s Guide 71 07117 000 Getting Started with Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 D2...

Page 5: ...es into the enclosure Do not make any connections yet Wire Length Wire Length for points is limited only by the resistance on the loop and potential EMI Electro Magnetic Interference problems Wire resistance on the Point 1 sensor loop must be less than 50Ω Measure the wire resistance before installing smoke detectors Short the end of line resistor before metering the wire Resistance on the sensor ...

Page 6: ...y required for fire and combined fire burglary systems In order to meet standby battery requirements use the Radionics D126 12v 7 0Ah battery for fire and combined fire burglary systems Charge the Battery as You Work Lock the Standby Switch Locking the pin in the standby position allows you to charge the battery as you install the detection devices and keypads Lock the pin down now See Figure 2 Wi...

Page 7: ...stems 1 Add together the current draws for all devices connected to the negative alarm output terminal This total is the current required for the Normal Standby Condition NSC This total must be less than 140mA 2 Subtract the NSC current required calculated in step 1 from the Primary Alarm Current 860mA The difference is the Alarm Current available for the Alarm Output terminals In formula format P...

Page 8: ...812 is a powered supervised point The panel monitors the Point 1 sensor loop for normal shorted or open conditions Programming determines how the panel responds to those conditions See the D2812 Program Entry Guide Terminal 11 provides positive voltage to 2 wire detection devices Terminal 12 the loop return is isolated from earth ground The Keypad Reset function interrupts power to this sensor loo...

Page 9: ...oute the power for the detectors through a D133 or D134 Relay Module The relay module must be connected to one of the panel s external relay outputs programmed for the reset function See RELAYS in the Program Entry Guide for programming instructions Heat Detectors and Other Dry Contact Initiating Devices Connect any number limited by the Authority Having Jurisdiction Burglary Devices Connect any n...

Page 10: ...e keypad or using the D5200 make sure the Standby Switch is locked down See Figure 8 If you re using the D5200 Figure 9 shows the location of the programming jack See the D5200 Programming Operation Manual for instructions on using the program mer Unlock the Standby Switch When you re finished programming move the Standby Switch to the normal position See Figure 8 The panel sends a RE BOOT report ...

Page 11: ...ailure The panel indicates an AC power restoral 60 seconds after power restores to the terminals labeled 16 5VAC Secondary DC Power A 12V 4 0 Ah sealed lead acid rechargeable battery Radionics D1240 supplies secondary power for auxiliary and alarm outputs The battery also powers the system during interruptions in primary AC power Lead Acid Batteries Only The panel charging circuit is only calibrat...

Page 12: ...his output until it times out or you perform a panel reset Extra Power for Keypads You may need to add one or more D8132 Battery Charger Power Supply Modules for the number of keypads you want to use Figure 10 shows the D8132 powering keypads in a stand alone configuration For UL Certificated accounts use a UL listed power supply The D8132 is not UL listed as a stand alone power supply for fire an...

Page 13: ...the POINT CODES Group in the Program Entry Guide for the correct programming for points used for keyswitches Installation Connect the end of line resistor for the point at the keyswitch so that the switch shorts the resistor when it operates An open on the circuit produces an alarm if the area is armed and a trouble if it is disarmed See Figure 12 Keyswitch Operation Shorting and restoring the poi...

Page 14: ...uctions You must use a 12 VDC option for the Easikey installation See Easikey Installation and Operation Instructions Easikey is not for use in UL installations Connect the Easikey door controller to the panel using a D133 Relay Module as shown in Figure 13 Make certain to connect the common for the Easikey s 12 VDC supply to the terminal labeled Aux on the panel Figure 13 Keyswitch www PDF Zoo co...

Page 15: ...llation documents to determine suitability When using four wire smoke detectors install a suitable power supervision unit according to the manufacturer s instructions Use the D133 or D134 Relay Module to provide reset capability In fire applications with one 7 0Ah 12 VDC battery the panel supports an auxiliary output of 140mA and a bell output of 720mA configured as necessary For additional loadin...

Page 16: ...otection must be provided The D2012 control panel is suitable for Central Station Grade C applications It is suitable for Central Station Grade B applications when the Model D2012 DACT unit is installed with a UL listed Local sounding device Also suitable for Central Station Mercantile Grade AA applica tions when installed with the Model D8122 derived channel subscriber terminal unit The D2012 con...

Page 17: ...res 24 hours of standby plus four minutes 067 hrs of alarm operation at the end of the 24 hour period You must use battery ampere hour Ah calculations to verify compliance The formula in the next column includes a 10 contingency factor for depletion of battery capacity with age NFPA 72 Chapter 2 Ampere Hour Calculation Formula Total B ___ x 24 Hrs Total C ___ x 067 Hrs 10 Contingency Total Ah requ...

Page 18: ... 30 _____ 125 _____ D223 _____ 30 _____ 30 _____ 140 _____ _______ _____ ___ _____ ___ _____ ___ _____ _______ _____ ___ _____ ___ _____ ___ _____ _______ _____ ___ _____ ___ _____ ___ _____ _______ _____ ___ _____ ___ _____ ___ _____ _______ _____ ___ _____ ___ _____ ___ _____ _______ _____ ___ _____ ___ _____ ___ _____ _______ _____ ___ _____ ___ _____ ___ _____ _____ Total A _____ Total B _____...

Page 19: ...32 122 F 0 50 C Relative Humidity 5 85 at 86 F 30 C non con densing Arming Stations D202A Keypad D205 Keypad D206 Keypad D220A Keypad D223 Keypad Keyswitch Easikey Compatible Enclosures D2803 Standard Enclosure D8103 Universal Enclosure D8109 Fire Enclosure D8108A Attack Resistant Enclosure Compatible Accessories See the Radionics Product Catalog for complete list D126 12V 7 Ah Rechargeable Batter...

Page 20: ...for continuously powered devices 500mA at 10 2 to 13 9 VDC Protected against overcurrent by self resetting device 8 Aux Aux Power Negative common for Aux Power and Relay Outputs 9 Ext1 External Relay 1 Connect D133 or D134 relay for Form C Dry Contact 10 Ext2 External Relay 2 Connect D133 or D134 relay for Form C Dry Contact 11 1 Positive Point 1 Positive Power for Point 1 Switched for sensor rese...

Reviews: