7.3.5. How to read the flue gas temperature
If you want to read the flue gas temperature, follow the steps below.
Picture 30. Flue gas temperature reading
7.4. Errors while starting the boiler
All possible errors in the initial operation phase, that is during ignition can be split into
three big groups:
Group I
Errors during ignition relating to the situation without sparks, smoke, or any
flame for more than 20 minutes from the moment of starting the ignition heater.
Group II
Errors during ignition relating to the situation in which flame appeared but
the boiler shut itself down after a certain period (a few minutes).
Group III
The boiler successfully ignited and was working for a few hours. Reached
the set temperature and, for a longer time, there is no need to turn on neither the dosing
system nor the fan (this situation is mostly overnight). Right after, the temperature is
dropping and the user wants a higher temperature (mostly in the morning), and the
boiler receives a signal to enter the ignition phase, but there is no flame.
Group I
Possible
cause 1
.
PROBLEM 1 –
The flap of the fan for primary air is closed. The fan is located on the
doser.
How to solve
PROBLEM 1
– Open the flap completely.
Possible
cause 2
.
PROBLEM 2 –
The hose connecting air channels from the fan to the heater is not
properly set.
How to solve
PROBLEM 2
– Affix the air hose both to the case of the heater and to
the air channel pipe.