EM-2H2RNY NY EMERGENCY LIGHT

EM-2H2RNY

M

I PORTANT

CAREFULLY BEFORE INSTALLING FIXTURE. R TAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.

 

READ 

E

IMPORTANT SAFEGUARDS:

When using electrical equipment, basic safety precautions should always be followed including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

• Do not use outdoors.
• Do not let power supply cords touch hot surfaces.
• Do not mount near gas or electric heaters.
• Equipment should be mounted securely in locations and at heights where it will not be readily subjected to tampering by 
  unauthorized personnel.
• The use of accessory equipment and replacement parts not recommended by the manufacturer may cause an unsafe condition.
• Do not use this equipment for other than its intended purpose.
• The AC voltage rating of this equipment is specified on the product label. Do not connect equipment to any other voltage.

RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is
required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON
FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.

INSTALLATION

1. Remove the front cover.
2. Mount the equipment securely in place on the wall. Two additional 
    Key Hole mounting holes are located at the top of the unit housing 
    in addition to the J-Box mounting holes. These 2 additional 
    mounting slot holes must be used when the unit is mounted to the 
    wall. Additional chain suppor t may be required by local codes. 
    Chain hook holes are provided at each end of the enclosure.
3. Extend 24 hr AC supply of rated voltage to the equipment, which is 
    furnished with a dual voltage 

(120/277V)

 field selectable input. 

    Connect unit to utility power using an approved connector. For 120V 
    supply connect the line wire to the Black lead and for 277V supply 
    connect the line wire to the Red lead. Connect neutral wire to the 
    White lead. The Ground wire 

(green lead)

 needs to be connected in 

    accordance with the local codes. DO NOT energize the circuit at this 
    time. CAUTION: Insulate the unused Black or Red wire. Failure to do so 
    may cause an unsafe condition.
4. If remote fixtures are to be connected to the equipment extend the 
    remote circuit in accordance with Ar ticle 700 and 720 of the National 
    Electric Code 

(NEC)

 and connect to the yellow and violet leads coming 

    out of the unit. CAUTION: The minimum wire size required by the NEC 
    is 12 gauge Copper or equivalent. Your installation may require larger 
    sized wire to ensure that the voltage drop DOES NOT exceed 5%. Do 
    not exceed the total output rating of the equipment including any
    additional mounted heads.
5. Install and connect the battery.
6. Energize the unit with AC supply. The charge indicator will illuminate.
7. Replace the unit cover.
8. Adjust and focus the lighting heads as required.

OPERATION

1. To test the equipment, depress the TEST switch. The charge 

(LED)

 

    indicator will turn OFF and the emergency lights will illuminate.
2. Once you release the TEST switch the emergency lights will turn OFF 
    and the charge (LED) indicator will illuminate.
3. The automatic charger will retur n into action, charging the battery 
    and trying to maintain it in a fully charged state.

NOTE: 

Allow the battery to charge for a minimum of 24 hrs after 

installation or after a power failure before conducting a 90-minute test 

(see TESTING section)

.

CAUTION: 

This equipment is furnished with a sophisticated solid state 

transfer switch which will automatically disconnect the emergency 
lights from the batter y if the batter y has been discharged to the end
of its useful output.

WARNING: 

Unused wires must be capped using enclosed wire nuts.