3
FOR THE PLUMBER
PLEASE NOTE this water heater is supplied factory set at 50 °C outlet hot water temperature to comply with
the requirements of
AS 3498.2009
.
This water heater requires a tempering valve to be installed.
Please follow all the installation instructions in the Installation and operating instructions handbook and the
following additional instructions for the water heater outlet connection.
1.
When connecting the hot water supply to the fixtures
in the property a minimum of 1.4 metres of pipe
-
work must be used between the outlet of the water
heater and the first tap and outlet. See Diagram to the
right.
2.
The Hot water line should be insulated with Ensolex or
similar pipe insulation.
3.
When the installation is completed the temperature is
to be tested at the taps to confirm the water tempera
-
ture does not exceed the required 50°C setting.
• Total length to
first tap or outlet
is required to be a
minimum of 1.4
metres from the
outlet connection of
the water heater.
•
Pipe size is nominal
18 mm from hot
water outlet to the
first tap or outlet.
First tap or outlet
SPECIFICATIONS
MODELS
QI-6S-20
QI-6S-26
Gas Input MJ/h
160
195
Inlet Pressure
kPa – Nat. Gas
1.13 min.
2.75 max.
1.13 min.
2.75 max.
Inlet Pressure
kPa - LPG
2.75 min./max
2.75 min./max.
Water Supply Pressure
kPa
150* min.
1200 max
150* min.
1200 max.
Height mm
542
542
Depth mm
170
215
Width mm
350
350
Weight kg
15.7
17.2
Gas Connection mm
20 BSP
20 BSP
Water Connections
15 BSP
15 BSP
Ignition
Electronic
Electronic
Electrical Supply V
240 AC
240 AC
NOTES:
* The appliance will operate at reduced performance below 340 kPa.
• For information relating to burner test point pressures and injector sizes, refer to the rating plate
located on the right hand side of the cabinet for each model. (Please refer to p. 7.)
• For information relating to overall dimensions and connection points refer to diagrams. (Please refer
to p. 5)
• Before installing in areas over 1500 m above sea level, contact the manufacturer for instructions.