ActiveScale™ X100 Site Requirements Guide
25
Output Voltage
Branch Circuit Characteristics
Output Connector Ratings
Dimensions and weights
2.3.6 Load balancing PDUs
When selecting a PDU for use with the ActiveScale X100 it is important to consider how to balance the
electrical load of the system on the PDU to prevent damaging power equipment or the system itself.
2.4 Build space requirement for rackless systems
The rackless version of ActiveScale X100 is designed to be delivered on multiple pallets and installed on
site. Because of this, it is important to be sure that enough space is available for the individuals that will
build the system to work.
While installing system components, there needs to be a minimum of 1220mm (48") of space at the front
of the rack to allow for the space needed for the largest system component to be installed by a two people.
Nominal
230VAC
Operating Range
220VAC-240VAC
Number of Branches
2
Total Available Steady State Current (per branch)
16A, balanced
Short Term Peak (per branch)
<=20A
C13 Steady State Current
10A
C13 Short Term Peak Current
15A
C19 Steady State Current
16A
C19 Short Term Peak Current
20A
Width
2.2 in. / 55 mm
Height
69 in. / 1753 mm
Depth
2.25 in / 57 mm
Weight
18 lbs. / 8.2 kg