Output Voltage

Branch Circuit Characteristics

Output Connector Ratings

Dimensions and weights

2.3.6  Load balancing PDUs

When selecting a PDU for use with the ActiveScale X100 it is important to consider how to balance the 

electrical load of the system on the PDU to prevent damaging power equipment or the system itself.

2.4  Build space requirement for rackless systems

The rackless version of ActiveScale X100 is designed to be delivered on multiple pallets and installed on 

site. Because of this, it is important to be sure that enough space is available for the individuals that will 

build the system to work.
While installing system components, there needs to be a minimum of 1220mm (48") of space at the front 

of the rack to allow for the space needed for the largest system component to be installed by a two people.

Nominal

230VAC

Operating Range

220VAC-240VAC

Number of Branches

2

Total Available Steady State Current (per branch)

16A, balanced

Short Term Peak (per branch)

<=20A

C13 Steady State Current

10A

C13 Short Term Peak Current

15A

C19 Steady State Current

16A

C19 Short Term Peak Current

20A

Width

2.2 in. / 55 mm

Height

69 in. / 1753 mm

Depth

2.25 in / 57 mm

Weight

18 lbs. / 8.2 kg

Summary of Contents for ActiveScale X100

Page 1: ...ActiveScale X100 Site Requirements Guide 6 68842 04 Rev A with ActiveScale OS 6 1 0 software...

Page 2: ...uantum Corporation and its affiliates in the United States and or other countries All other trademarks are the property of their respective owners Quantum specifications are subject to change TRADEMAR...

Page 3: ...Miscellaneous requirements 18 2 3 5 Example configurations 19 2 3 5 1 3 Phase Delta 208V 24A NA Japan Input Power Configuration 19 2 3 5 2 3 Phase Delta 208V 48A NA Input Power Configuration 21 2 3 5...

Page 4: ...ActiveScale X100 Site Requirements Guide 4...

Page 5: ...e 2 1 Relevant System Specs for Rack Requirements 14 Table 2 2 System Power Requirements 15 Table 2 3 Component Power Measurements 15 Table 2 4 Recommended startup order 19 Table 2 5 Contents of Activ...

Page 6: ...ActiveScale X100 Site Requirements Guide List of tables 6...

Page 7: ...ActiveScale X100 Site Requirements Guide List of figures 7 List of figures Figure 2 1 Minimum Servicing Space Required 28...

Page 8: ...ActiveScale X100 Site Requirements Guide List of figures 8...

Page 9: ...pter defines the scope of this document and provides a brief overview of the system site requirements It also lists the regulatory compliance information relevant to the product Topics Scope on page 1...

Page 10: ...with data growth and deliver on your business objectives The minimum configuration is equipped with one sled column in all six Storage Enclosure Basics and provides either 0 84 PB of data storage capa...

Page 11: ...3 configuration typical max 4 45 5 34 kW Base 4 configuration typical max 5 1 6 02 kW Base 5 configuration typical max 5 75 6 7 kW Full Base 6 configuration typical max 6 4 7 4 kW System Expansion Nod...

Page 12: ...column of populated sleds 19 59 22 91 KBTU h Full configuration base 6 seven columns of populated sleds 21 83 25 25 KBTU h System Expansion Node kit 1 0 665 to 0 785 KBTU hour Weight Minimum system w...

Page 13: ...t that a user must address in order to support the installation and operation of the system Topics Airflow considerations on page 14 Rack requirements on page 14 PDU requirements for rackless systems...

Page 14: ...ed for a base system dynamic loads if the system will be moved from its installation location and the additional Storage Sleds that might be added later if the system is scaled up Cable Management the...

Page 15: ...onfigurations that will not provide the required amount of power in a single connection For example there could be a lower power single phase PDU where one PDU cannot provide enough power for the Acti...

Page 16: ...configuration Locking Locking connector preferred Connector Locking Spec 5lbs force retention Protection Device Manually resettable circuit breaker Protection Compliance UL489 Protection Temperature C...

Page 17: ...input power configuration System Mounting Requirements Can be mounted in the rear of the rack and be contained fully within the outer dimensions of the rack except for the input power cord Neither th...

Page 18: ...is drawn that is sometimes several times its normal full load current This is called inrush current While inrush current might only last for microseconds it can still pose a risk to the system and ass...

Page 19: ...ompatibility EMC agency of the country that the rack is installed in Environmental Operating temperature 5 55 C 2 3 5 Example configurations The following sections provide examples of PDU configuratio...

Page 20: ...liant To NEMA L15 30P Input Plug Color Code N A Input Plug Ground Socket Position N A Input Cord Wire Gauge 10AWG or equivalent Nominal 208VAC Operating Range 200VAC 220VAC Number of Branches 3 Total...

Page 21: ...vailable 60A Input Power Available 17 3KW Input Wire Connections 3P PE 3 Poles plus Protective Earth 4 wire Input Plug Compliant To IEC 60309 1 IEC 60309 2 Input Plug Color Code Blue rated operating v...

Page 22: ...uency 50Hz Input Current Steady State Available 16A Europe International Input Current Peak Available 16A Input Power Available 11 0kVA at 230VAC 16Amp Input Wire Connections 4P PE 4 Poles plus Protec...

Page 23: ...4 Input Configuration 1 Phase Nominal Input Voltage line to neutral 208VAC Input Voltage Operating Range 200VAC 240VAC Nominal Frequency 60Hz Input Current Steady State Available 24A NA derated Input...

Page 24: ...g Number PDUs required by system including redundancy 4 Input Configuration 1 Phase Nominal Input Voltage line to neutral 230VAC Input Voltage Operating Range 220VAC 240VAC Nominal Frequency 50Hz Inpu...

Page 25: ...talled on site Because of this it is important to be sure that enough space is available for the individuals that will build the system to work While installing system components there needs to be a m...

Page 26: ...lbs Each Storage Enclosure Basic box Rail kit Chassis Sleds I O Module Power cables SAS cables Screws and fasteners 2 Pallet weight 250kg 550lbs Pallet Dimensions 965 x 1220 x 635mm 38 x 48 x 25in 2 x...

Page 27: ...65lbs Each Storage Node box Rail kits Screws and fasteners Storage Node Power cables 3 x System Nodes Box weight 30kg 65lbs Each System Node box Rail kits Screws and fasteners Storage Node Power cable...

Page 28: ...he system components will need to be moved through the facility until it reaches the data center or computer room where the system will be installed This section describes the considerations that the...

Page 29: ...rther assistance contact the Quantum Contact Support Center Region Support Contact North America 1 800 284 5101 toll free 1 720 249 5700 EMEA 1 800 7826 8888 toll free 49 6131 324 185 Asia Pacific 800...

Reviews: