ActiveScale™ X100 Site Requirements Guide
21
2.3.5.2 3-Phase Delta, 208V, 48A, NA Input Power Configuration
Input Current/Power
Input Connector and Wiring
Output Voltage
Branch Circuit Characteristics
Output Connector Ratings
Dimensions and weights
Number PDUs required by system including redundancy
2 ea.
Input Configuration
3-Phase Delta
Nominal Input Voltage (line-to-line)
208VAC
Input Voltage Operating Range
180VAC-220VAC
Nominal Frequency
60Hz
Input Current, Steady State Available
48A, North American de-rated
Input Current, Peak Available
60A
Input Power Available
17.3KW
Input Wire Connections
3P+PE (3-Poles plus Protective Earth), 4-wire
Input Plug Compliant To
IEC 60309-1, IEC-60309-2
Input Plug Color Code
Blue (rated operating voltage of 200 to 250)
Input Plug Ground Socket Position
3 hour position, mates with female in 9 hour position.
Input Cord Wire Gauge
6 AWG or equivalent
Nominal
208VAC, balanced
Operating Range
180VAC-220VAC, balanced
Number of Branches
6
Total Available Steady State Current (per branch)
13.9A, North American de-rated
Short Term Peak (per branch)
17.3A
C13 Stead State Current
12A, North America de-rated
C13 Short Term Peak Current
15A
C19 Stead State Current
16A, North America de-rated
C19 Short Term Peak Current
20A
Width
2.2 in. / 55 mm