ActiveScale™ X100 Site Requirements Guide
16
Input Cord
Delivered Power
Output Frequency
Output Connectors (Outlets)
Recommended Branch Circuit Protection
2.3.2 Mechanical requirements
Redundancy
The PDUs selected must have at least 35 receptacles available for ActiveScale X100 components.
Preferably, these would be split into two, redundant, PDUs, to protect the system from PDU or power
failure. Each component would have one connection to each PDU.
A single PDU should be able to support the full load of the system to adequately protect against PDU
failure. System shutdown and/or data loss may result if redundant PDUs are not utilized.
Length
3-meter length minimum
Estimated, Nominal Long Term
7kW
Estimated, Max Short Term (<= 1 hour)
7.6kW
Nominal
50Hz or 60Hz
Operating Range
47-63Hz
Compliant to
IEC 60320
Type
C13 (preferred) or C19 (All cables provided are C13 to C14)
Quantity
18 (may vary depending on configuration)
Locking
Locking connector preferred
Connector Locking Spec
5lbs force retention
Protection Device
Manually resettable circuit breaker.
Protection Compliance
UL489
Protection Temperature Characteristics Protection device trip current should be stable over operating temperature,
such as the behavior of a hydraulic magnetic circuit breaker
Short Circuit Protection
(line-to-line, if available)
The PDU should be able to withstand a line-to-line short- circuit at the end
of a 1.8M, 16AWG, C13 cord plugged into on one of its output connectors
without damage to the PDU or any smoke being emitted.
Short Circuit Protection
(line-to-neutral, if available)
The PDU should be able to withstand a line-to-line short- circuit at the end
of a 1.8M, 16AWG, C13 cord plugged into on one of its output connectors
without damage to the PDU or any smoke being emitted.
Short Circuit Protection
(line-to-ground)
The PDU should be able to withstand a line-to-neutral short-circuit at the
end of a 1.8M, 16AWG, C13 cord plugged into on one of its output
connectors without damage to the PDU or any smoke being emitted.