2.3 PDU requirements for rackless systems
PDUs are not supplied for the rackless version of ActiveScale X100. Follow these PDU requirements to
ensure that the system will function as designed. This section provides information that is necessary in
making the determination about selecting a PDU that will effectively and safely support the power
consumption of the system. The following table lists the power specifications of the system.
Table 2
-
2. System Power Requirements
Table 2
-
3. Component Power Measurements
2.3.1 PDU requirements, common
The system is configured to have two separate, AC source circuits to provide fully redundant power. Thus,
each source circuit must be able to provide the full power to the system. Typically, each source is provided
to a single socket wired into one of the customer's AC circuits. However, certain customers may have
power configurations that will not provide the required amount of power in a single connection. For
example, there could be a lower power single phase PDU where one PDU cannot provide enough power
for the ActiveScale X100 system. For these power configurations, up to two power connections will be
used for each “source” of the system.
Component Weights
Storage Enclosure Basic:
107kg/236lbs
Storage Node:
12.25kg/27bs
System Node:
12.25kg/27lbs
System Interconnect:
9kg/20lbs
Management Interconnect
1.9kg/4.14lbs.
Parameter
Minimum Configuration
Full Configuration
Power Connector Type
All connectors on each component are C14. The system comes with C13
to C14 cables. If these cables are not compatible with the site's selected
PDU and power equipment, the user must provide compatible cables.
Number of Connectors
35
35
Nominal System Power Required (W)
2.90kW
6.50kW
Maximum System Power Required (W) 4.0kW
7.60kW
Component
Average Active Power
Maximum Active Power
Management Interconnect
9W
9W
System Interconnect
83W
85W
System Node
196W
228W
Storage Node
200W
229W
Storage Enclosure Basic
804W
873W
Specification
Value
Summary of Contents for ActiveScale X100
Page 1: ...ActiveScale X100 Site Requirements Guide 6 68842 04 Rev A with ActiveScale OS 6 1 0 software...
Page 4: ...ActiveScale X100 Site Requirements Guide 4...
Page 6: ...ActiveScale X100 Site Requirements Guide List of tables 6...
Page 8: ...ActiveScale X100 Site Requirements Guide List of figures 8...