ActiveScale™ X100 Site Requirements Guide
11
1.3 System specification summary
The following table is a summary of specifications relevant to the ActiveScale X100.
Condition (fully configured)
Non-operating
Operating
Altitude
-984 ft to 39,3711 ft
(-300 m to 12,000 m)
-984 ft to 10,000 ft
(-300 m to 3048 m)
Packed system dimensions
•
Width
—41.4 in (1052 mm)
•
Depth
—61.41 in (1560 mm)
•
Height
—88.3 in (2243 mm)
Power requirements
N/A
Base configuration typical/max:
• 2.5/3.3 kW
Base +1 configuration typical/max:
• 3.15/3.98 kW
Base +2 configuration typical/max:
• 3.8/4.66 kW
Base +3 configuration typical/max:
• 4.45/5.34 kW
Base +4 configuration typical/max:
• 5.1/6.02 kW
Base +5 configuration typical/max:
• 5.75/6.7 kW
Full (Base +6) configuration typical/max:
• 6.4/7.4 kW
System Expansion Node kit:
1
• .195 to 0.23 kW
Rack units (U)
42U
2
Relative humidity
10% to 95% non-condensing
8% to 90% non-condensing
System dimensions
•
Width
—23.6 in (600 mm)
•
Depth
—52.6 in (1338 mm)
•
Height
—81.1 in (2060 mm)
System dimensions (without
doors)
•
Width
—23.6 in (600 mm)
•
Depth
—47.2 in (1200 mm)
•
Height
—81.1 in (2060 mm)
Temperature
40°F to 158°F
(-40°C to 70°C)
50°F to 95°F
(10°C to 35°C)
Temperature de-rating
33.8°F per 984.2 ft above 9842.5 ft
(1°C per 300 m above 3000 m)
33.8°F per 984.2 ft above 3116.8 ft
(1°C per 300 m above 950 m)
Temperature gradient
86°F (30°C)/hour
68°F (20°C)/hour