7

 

Adjustments 

 

The parameters can be changed on the 
control unit by means of the display and the 
joystick. 
The movements of the joystick have the following 
effects: 
• Vertical joystick movement (upward/downward) ->

 

Scroll through the displayed information. 

• Horizontal joystick movement (to the left/to the right) ->

 

Change the settings. 

• Shortly press in the joystick in the rest position 

-> 

Validation OK.

 

 

7.1

 

Motion parameters (PARAMETER) 

 

Parameter  Description 

Setting range 

Default 

Vo 

Opening speed (velocity open) 

0..14 (5…50°/s) 

Vc 

Closing speed (velocity close) 

0..14 (5…50°/s) 

TOEx 

Hold-open time opening element inside/outside (time hold 
opening element inside/outside) 

0...60 s 

3 s 

TKey 

Hold-open time Key (time hold opening element Key) 

0...180 s 

5 s 

TDelay 

Starting delay (time delay lock) 

0,0...4,0 s 

0,2 s 

FDelay 

Relieving force during unlocking (force delay), only effective 
if TDelay is > 0 

0,0...7,0 A 

OFF 

TLock 

Door rectification time (time press close) 

0,0...4,0 s 

0,5 s 

FLock 

Pressing force during locking (force lock), only effective if 
TLock is > 0 

0,0...7,0 A 

2,0 A 

FSlam 

Accelerating function (force slam) 

0...10 

OFF 

FWind 

Obstacle detection optimized for exterior doors (force 
wind) 

OFF 
OPEN 
CLOSE 
BOTH 

OFF 

Fo 

Opening force (force open) 

0...9 

Fc 

Closing force (force close) 

0...9 

Foh 

Hold-open force (force open hold) 

0...9 

Fch 

Interlocking force (force close hold)   automatically 
programs FLock and FDelay if these are 0 

0,0...3,5 A 

Ao 

Opening angle of the door (angle open) 
If the opening angle is changed during the operating mode 
OPEN, the operating mode MANUAL needs to be 
selected for closing the door. 

20...(190°) Rod dep. 

95° 

Rod 

Type of rods (Rod)                        
 
 
 

 
STD-PH 
SLI-PL 
SLI-PH 

STD-PH 
 

dAxis 

Distance between rotation axis of the door hinges and the 
mounting level of the drive unit (distance Axis). dAxis is an 
approximate value. Depending on the installation situation, 
dAxis may have to be adapted. 

-8...+25 cm 
Rod depending 

0/+8 cm 
Rod dep. 

 

 

Normal rods pushing function 
Sliding rods pulling function 
Sliding rods pushing function 

Summary of Contents for FD 10

Page 1: ...Swing door drive unit FD 10 pilot series Mounting and operating instructions Com no Pos Year of construction Operator Operating place...

Page 2: ...justments 19 7 1 Motion parameters PARAMETER 19 7 2 Configuration CONFIG 20 7 3 Installation with multiple door leaves Double Door 21 8 Menu navigation 22 8 1 PARAMETER 22 8 2 CONFIG 22 8 3 DOUBLE DOO...

Page 3: ...anent torque output shaft 56 Nm Short term torque output shaft 165 Nm Distance door hinge Output shaft Lintel mounting 100mm 160mm GSD Lintel depth Normal rods max 250mm Sliding rods pl 50 150 mm pull...

Page 4: ...tel mounting Lintel depth Option Axle extension Standard none 10 18 36 0548 190 10 10 28 46 0548 191 20 10 38 56 0548 192 30 10 48 66 0548 193 40 10 58 76 0548 194 50 10 68 86 adjust dimensions accord...

Page 5: ...the consequence that some measures will change 28mm and thus need to be adapted accordingly Lintel depth mm Max door opening angle 0 50 105 51 100 100 100 150 95 Option Axle extension Standard none 33...

Page 6: ...thus need to be adapted accordingly Option Axle extension Standard none 10 18 40 0548 190 10 10 28 50 0548 191 20 10 38 60 0548 192 30 10 48 70 0548 193 40 10 58 80 0548 194 50 10 68 90 adjust dimensi...

Page 7: ...e The fixing holes of the drive module must always be on the side facing the door hinge 2 Fasten the chassis by means of six screws M6 to lintel 3 Fasten the drive module by means of four screws M5 to...

Page 8: ...nction the arrow with description PULL points to the chassis 4 Route the reference switch cable the mains cable and program switch cable on the side cover below the drive module 5 Screw earth cable to...

Page 9: ...le the reference switch cable and program switch cable into the control unit c Fasten the control unit by means of three screws M5 to the chassis d For sliding rods with pulling function first release...

Page 10: ...ace side of the control unit 7 If required route the cable for sensors motor lock button etc below the drive module and the control unit and connect them 8 Mount the selected rods according to drawing...

Page 11: ...slight hit onto the screw heads b Open the door leaf to the desired maximum opening angle c Turn the stop piece till it stops and retighten the screws 6Nm 1 Open the door leaf and let it close by mea...

Page 12: ...t the power supply into the mains supply terminal b Fasten the power supplies with the strain relief clip onto the side cover c Insert mains cable into the mains supply terminal 3 Fasten both side cov...

Page 13: ...er commissioning a Degrease the glued surface on the covering b Remove white sticker protective sheet D c Affix the stencil B with the Logo C on the lower right corner of the covering and press on wel...

Page 14: ...only act upon the Master single leaf operation Opening elements connected to Slave act upon the Master as well as on the Slave bi parting operation The safety elements SER and SES are connected to th...

Page 15: ...desired time lag of the closing angle Note In cases where a mechanical closing sequence regulator is used start with a AcSeq of 90 6 Configuration of the Slave drive unit DubleD SlaveA AoSeq desired t...

Page 16: ...tic closing upon expiration of the adjustable hold open time MANUAL position 0 The drive mechanism and the control elements are switched off The door leaf can be manually opened The door leaf is close...

Page 17: ...ward once the display direction is switched to a readable position 3 Programming the type of rods Rod Move the joystick to the left to the right Validate the correct type of rods by means of OK In the...

Page 18: ...ed closing direction 11 Upon completion of the first learning run the following message is displayed 12 The display should immediately supply the following information 13 By means of an opening comman...

Page 19: ...Door rectification time time press close 0 0 4 0 s 0 5 s FLock Pressing force during locking force lock only effective if TLock is 0 0 0 7 0 A 2 0 A FSlam Accelerating function force slam 0 10 OFF FWi...

Page 20: ...e if relay PCB 0 is plugged in OPEN RC 0 3 Parametrizable relay output 3 on optional PCB 1 only visible if relay PCB 0 is plugged in ERROR RC 0 4 Parametrizable relay output 4 on optional PCB 1 only v...

Page 21: ...eD Closing sequence role Master Slave and interlock side A B OFF MastrA SlaveA MastrB SlaveB OFF AoSeq Current delay angle for opening sequence control Slave only visible if DubleD is active 0 110 20...

Page 22: ...etection EMY Emergency element PUGO Push and Go 2nd display line at the bottom left hand side the presently enabled operating mode is displayed a frame around the symbol indicates the overriding opera...

Page 23: ...s value is memorized 8 5 ERROR ACTIVE Pending active errors The pending active errors are displayed in a list This list is updated at the end and the latest additions appear during the next passage A0...

Page 24: ...any other joystick movement The setting up procedure can be canceled by means of the D BEDIX C key Setting of the opening angle Ao During the first setting up run the drive unit moves to the open posi...

Page 25: ...tching point of the reference switch The reference switch must be activated in the closed position switching contact open Open position F 02 Not detected in the closed position Prior to the first sett...

Page 26: ...resp under voltage E32 01 24 V Safety Over resp under voltage Overload short circuit 24 VDC onto terminals X105 or X107 E33 01 24 V E Lock Error Over resp under voltage Overload short circuit 24 VDC...

Page 27: ...ct the cabling of the opening elements LED SE safety element yellow is not lighted LED OE opening command blue is not lighted despite the active opening element The opening command is not evaluated Ch...