Section 4 - Installation
Quantech
39
Form QTC4-NM2
Issue date: 05/12/2023
4
Figure 18 -
Single point power wiring
Minimum circuit ampacity (MCA), Mini
-
mum/maximum fuse size, and minimum/
maximum circuit breaker size vary on
chillers based upon model and options
ordered. Consult YorkWorks or the chiller
data plate for electrical data on a specific
chiller.
Voltage utilization range
Rated voltage
Utilization range
200/60/3
180–220
230/60/3
208–254
380/60/3
342–418
400/60/3
360–440
460/60/3
414–508
575/60/3
520–635
400/50/3
360–440
Power supply wiring
Single point wiring
LD18588a
UNIT MOUNTED ELECTRONICS
INVERTER
1
INVERTER
2
LINE
REACTOR
UNIT CONTROLS
EVAPORATOR HEATER
FAN
CONTACTORS
TERMINAL BLOCK
(CIRCUIT BREAKER - OPT)
(NON-FUSED DISCONNECT
SWITCH - OPT)
STANDARD
CONTROL
TRANSFORMER
FIELD PROVIDED
UNIT POWER
SUPPLY
GN
D
SEE NOTE 1
WATER BOX
HEATER
KIT
115V/60Hz
220V/50Hz
L N
PE/GND
SEE NOTE 1
COMPRESSOR SYSTEM 1
COMPRESSOR SYSTEM 2
Note 1:
Dashed line represents customer wiring.
Summary of Contents for QTC40160
Page 22: ...Quantech 22 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 94: ...Quantech 94 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 100: ...Quantech 100 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 158: ...Quantech 158 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 187: ...Quantech 187 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...