51
QUANTECH
FORM QTC3-NM1
ISSUE DATE 08/03/2022
SECTION 5 – TECHNICAL DATA
55
TABLE 9 -
PUMP ELECTRICAL DATA (60 HZ)
PUMP
MODEL
HORSE
POWER RPM
PUMP ELECTRICAL DATA
208-3-60 HZ
230-3-60 HZ
380-3-60 HZ
460-3-60 HZ
575-3-60 HZ
FLA
LRA
FLA
LRA
FLA
LRA
FLA
LRA
FLA
LRA
A
5
3600
12.0
92.0
7.1
55.5
6.0
46.0
4.8
36.8
B
7.5
3600
17.6
126.0
10.6
78.0
8.8
63.0
7.0
50.4
C
10
3600
23.6
162.0
14.3
102.0
14.0
81.0
9.4
64.8
D
15
3600
35.0
232.0
20.9
143.0
17.5
116.0
14.0
92.8
E
5
1800
13.0
92.0
7.9
55.5
6.5
46.0
5.2
36.8
F
15
3600
35.0
232.0
20.9
143.0
17.5
116.0
14.0
92.8
G
7.5
3600
17.6
126.0
10.6
78.0
8.8
63.0
7.0
50.4
H
10
3600
23.6
162.0
14.3
102.0
14.0
81.0
9.4
64.8
I
15
3600
35.0
232.0
20.9
143.0
17.5
116.0
14.0
92.8
J
5
1800
13.0
92.0
7.9
55.5
6.5
46.0
5.2
36.8
K
15
3600
35.0
232.0
20.9
143.0
17.5
116.0
14.0
92.8
L
20
3600
45.0
290.0
28.7
190.0
22.5
145.0
18.0
116.0
M
3
1800
8.0
64.0
4.7
38.0
4.0
32.0
3.2
25.6
N
7.5
3600
17.6
126.0
10.6
78.0
8.8
63.0
7.0
50.4
O
10
3600
23.6
162.0
14.3
102.0
14.0
81.0
9.4
64.8
P
15
3600
35.0
232.0
20.9
143.0
17.5
116.0
14.0
92.8
R
5
1800
13.0
92.0
7.9
55.5
6.5
46.0
5.2
36.8
S
10
1800
24.0
162.0
15.1
102.0
12.0
81.0
9.6
64.8
T
15
1800
36.4
232.0
22.0
143.0
18.2
116.0
14.6
92.8
U
7.5
1800
18.4
126.0
11.1
78.0
9.2
63.0
7.4
50.4
V
20
3600
45.0
290.0
28.7
190.0
22.5
145.0
18.0
116.0
NOTES:
Reference PIN 59 for Pump Model.
Table 11 - Electrical Data Without Pumps on page 52
to determine electrical data of the unit plus the pump.
TABLE 10 -
TRANSFORMER LOAD
VA
VOLT
2000
3000
208
9.6
14.4
230
8.7
13.0
380
5.3
7.9
460
4.3
6.5
575
3.5
5.2
Summary of Contents for QTC3040T
Page 10: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 34: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 73: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 102: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 110: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 168: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...