SECTION 9 – SERVICE AND TROUBLESHOOTING
Form QCC2-NM1
Issue Date: 5/20/2021
9
This example indicates that the system 1 suction pres-
sure input is connected to plug 7 – pin 10 (J7-10) on
the I/O board. It indicates that the voltage is 2.1VDC
which corresponds to 81 psig (5.6 bars) suction pres-
sure.
The digital inputs will display the input connection and
ON/OFF status such as:
F L O W S W / R E M S T A R T
J
13
- 5 I S O
N
This indicates that the flow switch/remote start input is
connected to plug 13- pin 5 (J13-5) on the microboard,
and is ON (ON = +30 VDC unregulated input, OFF =
0VDC input on digital inputs).
Control inputs/outputs
Tables 24 through 27 are a quick reference list provid-
ing the connection points and a description of the in-
puts and outputs respectively. All input and output con-
nections pertain to the connections at the microboard.
Table 23 -
I/O Digital Inputs
J13-2
Unit ON/OFF Switch
J13-3
Load Limit Stage 2 on 3, 5 and 6 Comp. Units
J13-4
Load Limit Stage 1
J13-5
SYS 1 Zone Thermostat
J13-6
SYS 2 Zone Thermostat
J13-7
Single System Select
(Jumper = Single Sys, No Jumper = Two Sys)
J13-8
CR1
(Sys 1 Motor Protector/High Pressure Cutout)
J13-10
CR2
(Sys 2 Motor Protector/High Pressure Cutout)
Table 24 -
I/O Digital Outputs
TB7-2
SYS 1 Compressor 1
TB7-3
SYS 1 Liquid Line Solenoid Valve
TB7-4
SYS 1 Compressor 2
TB7-5
SYS 1 Compressor 3
TB7-7
SYS 1 Hot Gas Bypass Valve
TB10-2
SYS 2 Compressor 1
TB10-3
SYS 2 Liquid Line Solenoid Valve
TB10-4
SYS 2 Compressor 2
TB10-5
SYS 2 Compressor 3
TB7-8
SYS 1 Condenser Fan Output 1
TB7-9
SYS 1 Condenser Fan Output 2
TB7-10
SYS 1 Condenser Fan Output 3
TB10-8
SYS 2 Condenser Fan Output 1
TB10-9
SYS 2 Condenser Fan Output 2
TB10-10
SYS 2 Condenser Fan Output 3
TB8-2
Evaporator Heater
TB8-3
SYS 1 Alarm
TB9-2
SYS 2 Alarm
TB8-6 & 7
Evaporator Pump Starter
TB10-7
SYS 2 Hot Gas Bypass Valve
Table 25 -
I/O Analog Inputs
J7-10
SYS 1 Suction Transducer
J11-12
Unit Type: Chiller = NO Jumper J11-12 to +24VDC
QCC2 Condensing Unit = Jumper J11-12 to +24VDC
(Do NOT Use)
J7-11
SYS 1 Discharge Pressure Transducer (Optional)
J6-9
Ambient Air Temp. Sensor
J6-7
Leaving Chilled Liquid Temp. Sensor (Not Used)
J6-8
Discharge Air Temp Sensor
J9-10
SYS 2 Suction Pressure Transducer
J9-11
SYS 2 Discharge Pressure Transducer
J7-12
Unit/SYS 1 Voltage
J9-12
SYS 2 Voltage
Table 26 -
I/O Analog Outputs
N/A
Not Applicable
Summary of Contents for QCC2015CEE
Page 12: ...QUANTECH 12 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 38: ...QUANTECH 38 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 102: ...QUANTECH 102 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 171: ...QUANTECH 171 Form QCC2 NM1 Issue Date 5 20 2021 Notes...