96
www.qualitrolcorp.com
TransLife
TM
Control
allows you to configure the TransLife
TM
settings for the individual winding temperatures. It includes the fields described below.
TransLife
TM
Displays which of the three
TransLife
TM
tabs you have selected.
Enable /
Disable
Allows you to enable or disable the TransLife
TM
feature.
Winding
Temperature
Input Module
#
Allows you to select the number of the input module, or if suitably
equipped, the fiber optic probe that will measure the winding
temperature. This winding temperature measurement is used to calculate
the consumed life, the time to reach critical winding temperature, and the
values for the temperature profiler.
Ambient
Temperature
Input Module
#
Allows you to select the number of the RTD Input Module that will
measure the ambient temperature.
Note:
This field is only required if you are using the Critical Forecast
feature. It is not required for the Consumed Life or Temperature
Profiling features.
Oil
Temperature
Input Module
#
Allows you to select number of the RTD Input Module sensors that will
measure the oil temperature.
Note:
This field is only required if you are using the Critical Forecast
feature. It is not required for the Consumed Life or Temperature
Profiling features.
Load Current
Input Module
#
Allows you to select the number of the current input module sensors that
will measure the current load of the selected winding.
Note:
This field is only required if the winding temperature input module
is a direct-winding, fiber optic probe and you are using the Critical
Forecast feature. It is not required if the winding temperature
input module is not a fiber optic probe, or for the Consumed Life
and Temperature Profiling features.
Summary of Contents for 509ITM Series
Page 26: ...26 www qualitrolcorp com Current Input Wiring...
Page 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Page 101: ...101 www qualitrolcorp com...
Page 144: ...144 www qualitrolcorp com The following window will appear...
Page 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Page 178: ...178 www qualitrolcorp com Appendix...
Page 179: ......
Page 180: ......
Page 181: ......