Temperature Profiler
allows you to configure the Temperature
Profiler. The Temperature Profiler has 12 ranges of temperature values - six ranges each
above and below the value in the
Unity Temperature
field.
The Temperature Profiler monitors how many hours the measured winding temperature
remains in each temperature range. This provides you with a visual indication of how and
when the transformer has been used in conjunction with the consumed life value, and it
provides a more accurate indication of the total loss of life of the transformer.
The ranges are divided into six-degree increments, because the consumed life of a
transformer doubles for approximately every six degree rise in temperature.
The
Temperature Profiler
section includes the fields described below.
Unity
Temperature
Allows you to enter a temperature value where one hour of operating
time equals one hour of consumed life. If the Unity Temperature
parameter is unknown, use the recommended values from
Temperature
Legends
The 12 temperature legends are displayed after you:
1. Enter a temperature value in the
Unity Temperature
field.
2. Press [Load].
3. Re-enter the
TransLife
TM
Setup
window.
The legends will be in 12 ranges, 6 below the Unity Temperature and 6
above.
12
Temperature
Range Fields
Display the amount of hours the selected winding temperature remained
in each range.
Graph Button
Displays a bar graph of the 12 temperature ranges. The 6 blue ranges
indicate the operating times that exceeded the consumed life rate.
Conversely, 6 red ranges indicate the consumed life that exceeded the
operating time.
Summary of Contents for 509ITM Series
Page 26: ...26 www qualitrolcorp com Current Input Wiring...
Page 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Page 101: ...101 www qualitrolcorp com...
Page 144: ...144 www qualitrolcorp com The following window will appear...
Page 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Page 178: ...178 www qualitrolcorp com Appendix...
Page 179: ......
Page 180: ......
Page 181: ......