P
OWER
G
EN
O
PERATION
165
Table 20-3 Warning Light
Condition
Indication
Description
Off
No issues
1 short blink every 3
seconds
Low or no gas pressure
Resets automatically when gas pressure
recovers
2 short blinks every
3 seconds
Low coolant level
Resets automatically once coolant is
filled
3 short blinks
Bad NTC sensor
Triggered by any of the NTCs
Constant light
Cold start preheating
needed
Applicable for standard and low temp
start systems
On/off blinks
General warning
Warning type can be seen through Lynx
or SmartView
Table 20-4 Fault Light
Condition
Indication
Description
Off
No issues
1 short blink
E-stop or disconnect
switch
Detects if DC disconnect switch is OFF or
e-stop is activated (light will stop blinking
once e-stop disengages
2 short blinks every
3 seconds
Battery low
Internal battery voltage is below start
threshold
3 short blinks every
3 seconds
Fail to ignite while gas
pressure is in range
(Ignition Fault)
See Table 15-3
4 short blinks
Coolant low flow
Fault 13002 or 14003, see Table 15-8 for
more details
On/Off blinks
General fault
Contact customer support
Constant light
Output overload
Customer loads are overloading the
outputs of the PowerGen
WARNING:
The Local/Remote selector switch
allows the PowerGen to start remotely by any
external device when in REMOTE position. If you
are servicing the unit, it is advised to switch the
Power Disconnect switch to the “OFF” position,
after it is fully-disabled.
Summary of Contents for PowerGen 5650 Series
Page 1: ...7045 102089 000 June 1 2021 Installation Operation Manual FOR A QUALIFIED INSTALLER...
Page 8: ...iv...
Page 12: ...iv Figure 21 9 ATS Enclosure 179 Figure 21 10 Battery Connection Schematic 181...
Page 28: ...SYSTEM INTRODUCTION 16 Figure 3 6 P ID Diagram...
Page 69: ...QNERGY LYNX SOFTWARE 57 Figure 6 57 FPC FEB QEC Firmware Update...
Page 158: ...MAINTENANCE 146 Figure 17 2 Radiator and Over Flow Tank...
Page 194: ...POWERGEN OPTIONAL FEATURE SETS 182...