6QBI User’s Guide
UG-1091
26
•
Test Panel (Maintenance)
Copyright © 2021 QEI
15.5
Reading Analog Values (RA)
Analog points can be selected and displayed in real-time. You may use the panel
address to simplify point entry. To enter the desired analog points, proceed as
follows:
Example read single point:
RA 4 <enter>
Display:
[4]2000
Example read multiple points:
RA 0 3
Display:
[0]2000 [1]0136 [2]-2000 [3]0050
Example read multiple points as voltage:
RA 35 38 V
Display:
[35]+4.25v [36] -1.24v [37] -4.50v [38] 5.00v
Example read Panel 3 (AIP address) multiple points as voltage:
RA P3 0 4 V
Display:
[48]+4.25v [49] -1.24v [50] -4.50v [51] +5.00v
15.6
Reading Status Values (RS)
Status points can be selected and displayed in real-time. They are display as two (2)
8-bit registers. To enter the desired analog points, proceed as follows:
Example read single point:
RS 4 <enter>
Display:
[4] 00000000 00000000
Example read multiple points:
RS 0 2
Display:
[0]00000000 00000000 [1]10101010 01010101 [2]11111111 11111111
15.7
Reading Accumulator Values (RC)
The Test Panel can monitor up to eight (8) accumulator values at a time and display
changes in real-time as they occur.
Example read single accumulator point:
RC 0 <enter>
Display:
[0]00034
Example read range of accumulator points:
RC 10 15
Display:
[10]00034 [11]00100 [12]02890 [13]00000 [14]00089 [15]01000